Laserfiche WebLink
1991 UNIFORM BUILDING CODE 904,2,3.7 <br /> 904.4 <br /> EXCEPTIONS: 1. Sprinklers are not required for stages 1,000 904.2.7 Group I Occupancies. An automatic sprinkler system <br /> square feet(92.9 m2)or less in area and 50 feet(15 240 mm)or less in shall be installed in Group I Occupancies.In Group I,Division 1.1 <br /> height where curtains,scenery or other combustible hangings are not and Group I,Division 2 Occupancies,approved quick-response or <br /> retractable vertically.Combustible hangings shall be limited to a single residential sprinklers shall be installed throughout patient Slee <br /> main curtain,borders,legs and a single backdrop. P gh P P- <br /> 2.Under stage areas less than 4 feet(1219 mm)in clear height used mg areas. <br /> exclusively for chair or table storage and lined on the inside with EXCEPTION: In jails,prisons and reformatories,the piping sys. <br /> 5/8-inch(16 mm)Type X gypsum wallboard or an approved equal. tem may be dry,provided a manually operated valve is installed at a <br /> continuously monitored location.Opening of the valve will cause the <br /> 904.23.8 Smoke-protected assembly seating. All areas- piping system to be charged.Sprinkler heads in such systems shall be <br /> enclosed with walls and ceilings in buildings or structures con- equipped with fusible ei'emots or the system shall be designed as re- <br /> taining smoke-protected assembly seating shall be protected with quired for deluge systems in UBC Standard 9-1. <br /> an approved automatic sprinkler system. 904.2.8 Group b1 Occupancies. An automatic sprinkler system <br /> EXCEPTION:Press boxes and storage facilities less than 1,000 hall be installed in rooms cl ed as Gb1 <br /> Occupancies where <br /> square feet(92.9 m2)in area and in conjunction with outdoor seating s � Group P <br /> facilities where all means of egress in the seating area are essentially the floor area exceeds 12,000 square feet(1115 m2)on any floor or <br /> open to the outside. 24,000 square feet(2230 m'-)on all floors or in Group M Occupan- <br /> 904.2.4 Group E Occupancies. cies more than three stories in height.The area of mezzanines shall <br /> be included in determining the areas where sprinklers are <br /> 9042.4.1 General. An automatic fire sprinkler system shall be required. <br /> installed throughout all buildings containing a Group E,Division <br /> 1 Occupancy. 9042.9 Group R, Division 1 Occupancies. An automatic <br /> EXCEPTIONS: 1. When each room used for instruction has at sprinkler system shall be installed throughout every apartment <br /> ' least one exterior exit door at ground level and when rooms used for house three or more stories in height or containing 16 or more <br /> assembly purposes have at least one half of the required exits directly dwelling units,every congregate residence three or more stories in <br /> to the exterior ground level,a sprinkler system need not be provided. height or having an occupant load of 20 or more,acid every hotel <br /> 2.When area separation walls,or occupancy separations having a three or more stories in height or containing 20 or more guest <br /> fire-resistive rating of not less than two hours subdivide the building rooms.Residential or quick-response standard sprinklers shall be <br /> into separate compartments such that each compartment contains an used in the dwelling units and guest room portions of the building. <br /> aggregate floor area not greater than 20,000 square feet(1858 m2),an <br /> automatic sprinkler system need not be provided. 90.13 Sprinkler System Monitoring and Alarms. <br /> 9042.4.2 Basements. An automatic sprinkler system shall be 90.13.1 Where required. All valves controlling the water sup- <br /> installed in basements classified as Group E,Division 1 Occupan- ply for automatic sprinkler systems and water-flow switches on all <br /> cies. sprinkler systems shall be electrically monitored where the num- <br /> 904.2.4.3 Stairs. An automatic sprinkler system shall be in- ber of sprinklers are: <br /> stalled in enclosed usable space below or over a stairway in Group1. Twenty or more in Group I,Divisions 1.1 and 1.2 Occupan- <br /> E,Division 1 Occupancies.See Section 1005.3.3.6. cies. <br /> 904.2.5 Group F Occupancies. 2. One hundred or more in all other occupancies. <br /> Valve monitoring and water-flow alarm and trouble signals <br /> 904.2.5.1 Woodworking occupancies. An automatic fire sprin- shall be distinctly different and shall be automatically transmitted <br /> kler system shall be installed in Group F woodworking occupan- to an approved central station,remote station or proprietary moni- <br /> cies over 2,500 square feet(232.3 m-)in area that use equipment, toring station as defined by national standards,or,when approved <br /> machinery or appliances that generate finely divided combustible by the building official with the concurrence of the chief of the fire <br /> waste or that use finely divided combustible materials. _ department,sound an audible signal at a constantly attended loca- <br /> 904.2.6 Group H Occupancies. tion. <br /> EXCEPTION:Underground key or hub valves in roadway boxes <br /> 90.12.6.1 General. An automatic fire-extinguishing system provided by the municipality or public utility need not be monitored. <br /> shall be installed in Group H,Divisions 1,2,3 and 7 Occupancies. <br /> 9043.2 Alarms. An approved audible sprinkler flow alarm shall <br /> 904.2.6.2 Group H, Division 4 Occupancies. An automatic be provided on the exterior of the building in an approved location. <br /> fire-extinguishing system shall be installed in Group H,Division 4 An approved audible sprinkler flow alarm to alert the occupants <br /> Occupancies having a floor area of more than 3,000 square feet shall be provided in the interior of the building in a normally occu- <br /> (279 m'-). pied location.Actuation of the alarm shall be as set forth in UBC <br /> 904.2.63 Group H, Division 6 Occupancies. An automatic Standard 9-1. <br /> fire-extinguishing system shall be installed throughout buildings 904.4 Permissible Sprinkler Omissions. Subject to the ap- <br /> containing Group H,Division 6 Occupancies.The design of the proval of the building official and with the concurrence of the <br /> sprinkler system shall not be less than that required under UBC chief of the fire department,sprinklers may be omitted in rooms or <br /> Standard 9-1 for the occupancy hazard classifications as follows: areas as follows: <br /> LOCATION OCCUPANCY HAZARD 1. When sprinklers are considered undesirable because of the <br /> CLASSIFICATION nature of the contents or in rooms or areas that are of noncombus- <br /> Fabrication areas Ordinary Hazard Group 2 <br /> tible construction with wholly noncombustible contents and that <br /> Service corridors Ordinary Hazard Group 2 are not exposed by other areas. Sprinklers shall not be omitted <br /> Storage rooms without dispensing Ordinary Hazard Group 2 from any room merely because it is damp,of fire-resistive con- <br /> Storage rooms with dispensing Extra Hazard Group 2 struction or contains electrical equipment. <br /> ' Corridors Ordinary Hazard Group 21 2. Sprinklers shall not be installed when the application of wa- <br /> When the design area of the sprinkler system consists of a corridor protected ter or flame and water to the contents may constitute a serious life <br /> by one row of sprinklers,the maximum number of sprinklers that needs to Y <br /> be calculated is 13. or fire hazard,as in the manufacture or storage of quantities of alu- <br /> 1-95 <br />