Laserfiche WebLink
• <br /> RHVAC-Residential&Light Commercial HVAC Loads Program • Elite Software Development,Inc. <br /> ;Ditter,ince"" Whitten <br /> Flame',MN 55340-9691 Page 2 <br /> Project Summary <br /> Project: Whitten Company: Ditter Inc. Cooling & Heating <br /> Client: Ben Whitten Representative: Doug Bjork <br /> Address: 1889 West Farm Rd. Address: 820 Tower Drive <br /> City: Orono, MN. City: Hamel, MN. 55343 <br /> Phone: Phone: 478-9558 <br /> Fax: Fax: 478-2426 <br /> Comment: <br /> Design Data <br /> Project Name: Whitten <br /> Reference City: Minneapolis, Minnesota <br /> Daily Temperature Range: Medium <br /> Latitude: 44 Degrees <br /> Elevation: 834 Feet <br /> Elevation Sensible Adj. Factor: 1.000 <br /> Elevation Total Adj. Factor: 1.000 <br /> Outdoor Outdoor Indoor Indoor Grains <br /> Dry Bulb Wet Bulb Rel.Hum. Dry Bulb Difference <br /> Winter: -20 N/A N/A 72 N/A <br /> Summer: 95 75 50% 75 36 <br /> Check Figures <br /> Total Building Supply CFM: 1059 CFM per square foot: 0.772 <br /> Square feet of room area: 1,372 Square feet per ton: 547.836 <br /> Building Loads <br /> Total heating required with outside air: 71,341 Btuh 71.341 MBH <br /> Total sensible gain: 23,141 Btuh 85 % <br /> Total latent gain: 4,229 Btuh 15 % <br /> Total cooling required with outside air: 27,369 Btuh 2.281 Tons (based on sensible + latent) <br /> 2.504 Tons (based on 77% sensible capacity) <br /> Notes <br /> Calculations are based on 7th edition of ACCA Manual J. <br /> All computed results are estimates as building use and weather may vary. <br /> Be sure to select a unit that meets both sensible and latent loads. <br /> Thursday,December 31, 1998 <br />