Laserfiche WebLink
Often Brothers Addition <br /> Code Review <br /> October 14, 1998 <br /> Page Two <br /> Projections of Non-Combustible <br /> Materials Sec 705 <br /> Chapter 10 <br /> Occupant Load <br /> Addition 17,808/30= 594 occ. <br /> Two Exits Required Yes <br /> Width .2 (594)= 119" <br /> Illuminated Exit Signs Required with <br /> Battery Backup <br /> Doors, special doors for exiting Not Allowed when <br /> Sec 1003.3.1.2 Over 50 occupants <br /> Door Leaf width shall not exceed 4' <br /> Sec 1003.3.1.4 <br /> Doors must swing out <br /> Sec 1003.3.1.5 <br /> Landings at doors required <br /> Sec 1003.3.1.7 <br /> Door to comply with <br /> Sec 1003.3.1.8 <br /> Panic hardware not required <br /> Three exits required <br /> Sec 1004.2.3.4 <br /> Travel distance maximum 250' <br /> Sec 1004.2.5.2.2 <br /> I hereby certify that this report was prepared by me or under my supervision,and that I am a duly <br /> registered architect under the laws of the State of Minnesota. <br /> odd Moha , IA Registration Number: 18074 <br /> Iu(OHISYSVOBSIOTTENIdocicode rev.doc <br />