Laserfiche WebLink
• <br /> ARI capacity ratings (cont) carrier <br /> . a <br /> HEATING CAPACITIES AND EFFICIENCIES - 48TJ004-014 <br /> HEATING INPUTTEMPERATURE STEADY-STATE CALIFORNIA <br /> (Btuh) OUTPUT CAPACITY AFUE EFFICIENCY SEASONAL <br /> UNIT 48TJ StagRI <br /> 2/Stage 1 (Btuh) RISE (%) (%) EFFICIENCY <br /> (%) <br /> 004 -/ 72,000 59,200 25-55 80.0 80.0 77.2 <br /> F004 115,000/ 82,000 92,000 55-85 80.0 80.0 76.7 <br /> 11"141111.- D005 -/ 72,000 59,200 25-55 80.0 80.0 77.2 <br /> 005 -/115,000 92,000 35-65 80.0 80.0 77.1 <br /> F005 150,000/120,000 120,000 50-80 80.0 80.0 76.9 <br />®)bD006 -/ 72,000 59,200 25-55 80.0 80.0 77.2 <br /> c006 -/115,000 92,000 35-65 80.0 80.0 77.1 <br /> F006 150,000/120,000 120,000 50-80 80.0 80.0 76.9 <br /> 1111111007 -/ 72,000 59,200 25-55 80.0 80.0 77.2 <br /> 007 -/115,000 92,000 35-65 80.0 80.0 77.1 <br /> F007 150,000/120,000 120,000 50-80 80.0 80.0 76.9 <br /> D008 -/125,000 100,000 20-50 80.0 80.0 75.8 <br /> E008 180,000/120,000 144,000 35-05 80.0 80.0 77.1 <br /> F008 224,000/180,000 179,200 45-75 80.0 80.0 77.1 <br /> D009 -/125,000 100,000 20-50 80.0 80,0 75.8 <br /> E009 180,000/120,000 144,000 35-65 80.0 80.0 77.1 <br /> F009 224,000/180,000 179,200 45-75 80.0 80.0 77.1 <br /> 0012 180,000/120,000 144,000' 35-65 80.0 80.0 77.1 <br /> E012 224,000/180,000 179,200 35-65 80.0 80.0 77.1 <br /> • <br /> F012 250,000/200,000 200,000 40-70 80.0 80.0 76.4 <br /> 0014 224,000/180,000 179,200 35-65 80.0 80.0 77.1 <br /> E014 250,000/200,000 200,000 40-70 80.0 80.0 76.4 <br /> LEGEND <br /> AFUE-Annual Fuel Utilization Efficiency <br /> NOTE: NOx levels are 40 nanograms/joule with the accessory NOx reduction kit(sizes 004-014). <br /> HEATING CAPACITIES AND EFFICIENCIES - 48TJ016-028 <br /> HEATING INPUTOUTPUT CAPACITY TEMPERATURE STEADY-STATE MINIMUM <br /> UNIT 48TJ (Btuh) (Btuh) RISE EFFICIENCY HEATING <br /> Stage 2/Stage 1* (F) (%) CFM <br /> D016 230,000/172,000 186,000 15-45 81.0 3800 <br /> F016 300,000/225,000 243,000 30-60 81.0 3800 <br /> 0020 275,000/206,000 223,000 15-45 81.0 4750 <br /> F020 360,000/270,500 292,000 20-50 81:0 5450 <br /> 0024 275,000/206,000 223,000 15-45 81.0 4750 <br /> F024 360,000/270,000 292,000 20-50 81.0 5450 <br /> 0028 275,000/206,000 223,000 15-45 81.0 4750 <br /> F028 360,000/270,000 292,000 20-50 81.0 5450 <br /> 'All units are 2-stage heat. <br /> NOTE: Minimum allowable temperature of mixed-air entering the heat exchanger during first-stage <br /> heating is 45 F.There is no minimum mixed-air temperature limitation during second-stage heating. <br /> c <br />