Laserfiche WebLink
WCC0301 June 4,2004 <br /> Wayzata Country Club Addition! Renovation Page 5 <br /> 19. Sheet A670, Detail 2B: The employee's lavatory counter does not appear to meet accessibility <br /> requirements. Has this been approved? <br /> MDA to issue a revised detail indicating 29"min. clear from the finished floor to the bottom of the apron and 34"to <br /> the rim of the sink above finished floor. <br /> 20. Sheet F101: It has been our recent experience that an elevator inspector has objected to a single sprinkler <br /> pipe serving the elevator equipment room and then continuing through to serve the elevator pit. Please verify that <br /> the proposed design is acceptable. <br /> Also, please clarify locations of sprinkler heads in Stair C. <br /> Comments from Mechanical pending. <br /> 21. Sheet M101: <br /> A. No ventilation appears to be provided for the elevator equipment rooms. Is ventilation required? <br /> (Typically we have been required to provide mechanical ventilation to maintain ambient temperature and humidity <br /> per manufacturer's specifications per 2000 ASME 17.1 Section 2.7.5.2 or similar.) If so, are combination <br /> Fire/Smoke dampers required? <br /> B. Do the ducts entering the shaft at approximately Gridline 11 between L and M require dampers? This <br /> may be subject to City interpretation of IBC 715.6.3 and related sections. <br /> Comments from Mechanical pending. <br /> 22. Sheet M103, Detail 2: It appears that piping, which does not serve the stair enclosure, is passing through <br /> the enclosure. Should this detail be revised? <br /> Comments from Mechanical pending. <br /> 23. Sheet E101: Is emergency lighting to be provided in the elevator equipment room and is said lighting <br /> adequate in the employee break room? <br /> Comments from Electrical pending. <br /> U:\WCC\WCC0301\Documentation\H-Prime Contr\H1 Contractor Correspondence\Document Review.doc <br />