Laserfiche WebLink
705.11 —707.1 FIRE-RESISTANCE-RATED CONSTRUCTION <br /> 705.11 Ducts and air transfer openings. Ducts and air storage as provided for in Section 415.7.2.1 shall be <br /> transfer openings shall not penetrate fire walls. 2 hours,but not less than required by Table 601 for <br /> the building construction type. <br /> Exception:Penetrations by ducts and air transfer openings of 2. Shaft enclosure shall be permitted to terminate at a <br /> fire walls that are not on a lot line shall be allowed provided top enclosure complying with Section 707.12. <br /> the penetrations comply with Sections 711 and 715.The size <br /> and aggregate width of all openings shall not exceed the lim- 706.5 Exterior walls.Where exterior walls serve as a part of <br /> itations of Section 705.8. <br /> a required fire-resistance-rated enclosure, such walls shall <br /> SECTION 706 comply with the requirements of Section 704 for exterior <br /> FIRE BARRIERS walls and the fire-resistance-rated enclosure requirements <br /> shall not apply. <br /> 706.1 General. Fire barriers used for separation of vertical exit <br /> enclosures, exit passageways, horizontal exits, incidental use Exception: Exterior walls required to be fire-resistance <br /> areas, to separate different occupancies or to separate a single rated in accordance with Section 1005.3.6.5. <br /> occupancy into different fire areas,shall comply with this section. <br /> 706.2 Materials.The walls and floor assemblies shall be of 706.6 Openings.Openings in a fire barrier wall shall be pro- <br /> materials permitted by the building type of construction. tected in accordance with Section 714. Openings shall be <br /> limited to a maximum aggregate width of 25 percent of the <br /> 706.3 Fire-resistance rating. The fire-resistance rating of length of the wall,and the maximum area of any single open- <br /> the walls and floor assemblies shall comply with this section. ing shall not exceed 120 square feet(11 m2).Openings in exit <br /> enclosures shall also comply with Section 1005.3.4. <br /> 706.3.1 Vertical exit enclosure.The fire-resistance rating <br /> of the separation between building areas and a vertical exit Exceptions: <br /> enclosure shall comply with Section 1005.3.2. 1. Openings shall not be limited to 120 square feet(11 <br /> 706.3.2 Exit passageway.The fire-resistance rating of the m22) where adjoining fire areas are equipped <br /> separation between building areas and an exit passageway throughout with an automatic sprinkler system in <br /> shall comply with Section 1005.3.3. accordance with Section 903.3.1.1. <br /> 706.3.3 Horizontal exit.The fire-resistance rating of the 2. Fire doors serving an exit enclosure. <br /> separation between building areas connected by a hori- 3. Openings shall not be limited to 120 square feet(11 <br /> zontal exit shall comply with Section 1005.3.5. m2) or an aggregate width of 25 percent of the <br /> length of the wall where the opening protective <br /> 706.3.4 Incidental use areas.The fire barrier separating assembly has been tested in accordance with ASTM <br /> incidental use areas shall have a fire-resistance rating of E 119 and has a minimum fire-resistance rating not <br /> not less than that indicated in Table 302.1.1. less than the fire-resistance rating of the wall. <br /> 706.3.5 Separation of occupancies.The fire barrier sep- <br /> arating mixed occupancies,or a single occupancy into dif- 706.7 Penetrations. Penetrations through fire barriers shall <br /> ferent fire areas, shall have a fire-resistance rating of not comply with Section 711. <br /> less than that indicated in Section 302.3.3 based on the <br /> occupancies being separated. 706.7.1 Prohibited penetrations. Penetrations into an <br /> 706.4 Continuity. Fire barriers shall extend from the top of exit enclosure shall only be allowed when permitted by <br /> the floor/ceiling assembly below to the underside of the floor Section 1005.3.4.1. <br /> or roof slab or deck above and shall be securely attached <br /> thereto. These walls shall be continuous through concealed 706.8 Joints. Joints made in or between fire barriers shall <br /> spaces such as the space above a suspended ceiling.The sup- comply with Section 712. <br /> porting construction shall be protected to afford the required <br /> fire-resistance rating of the fire barrier supported except for 706.9 Ducts and air transfer openings. Penetrations by <br /> 1-hour fire-resistance-rated incidental use area separations as ducts and air transfer openings shall comply with Sections <br /> required by Table 302.1.1 in buildings of Types IIB,IIIB and 711 and 715. <br /> VB construction. Hollow vertical spaces within the fire bar- <br /> rier wall shall be firestopped at every floor level. SHAFT ENCLOSURES <br /> Exceptions: <br /> 1. The maximum required fire-resistance rating for 707.1 General.The provisions of this section shall apply to <br /> assemblies supporting fire barriers separating tank vertical shafts where such shafts are required to protect open <br /> 100 2000 INTERNATIONAL BUILDING CODE® <br />