Laserfiche WebLink
PASSIVE MAKE-UP AIR OPENING SCHEDULE <br /> TABLE FOR SIZING,PASSIVE MAKE-UP AIR OPENINGS Diameter - Path 0 Path 1 Path 2 <br /> Notes: a) This table assumes 20 feet of smooth unobstructed round 3 inches ' 50 cfm 35 cfm . 15 cfin <br /> duct with three 90°elbows and a screened hood 4 inches 90 cfm 60 cfin 30 cfm , <br /> b) Equivalent designs calculated using pressures of 50 Pascals 5 inches 140 cfm 100 cfm 45 cfm <br /> for Path 0, 25 Pascals for Path 1, and 5 Pascals for Path 2 6 inches 200 cfm .140 cnn 65 cfm <br /> may be used. 7 inches 270 cfm 190 cfm 85 cfin <br /> c) If a make-up air opening is used with no duct or elbows,the 8 inches 350 cfm 250 cfm 110 cfin <br /> diameter can be decreased by 1 inch. 9 inches 450 cfm 320 cfm 140 cfm <br /> d) If flex duct is used,increase diameter by 1 inch. 10 inches 570 cfin_ 400 cfm 180 cfin <br /> Make-up Air Application/Location CFM Opening size Duct Type - <br /> ❑ Smooth ❑ Flex ❑ Opening only <br /> ❑ Smooth ❑ Flex ❑ Opening only <br /> ❑ Smooth ❑ Flex ❑ Opening only <br /> ❑ Smooth ❑Flex ❑ Opening only <br /> AGGREGATE MAKE-UP AIR WORKSHEET <br /> INSTRUCTIONS • <br /> Step 1. Complete Exhaust Schedule on the right indicating cfm of largest device in each category. EXHAUST SCHEDULE <br /> Step 2. Complete the Combustion Equipment Schedule on preceding page. DEVICE CFM <br /> Step 3. Choose a path with a Y(Yes)for all selected equipment. Clothes dryer. <br /> Step 4. _Complete Aggregate Make-up Air table below for chosen path.Using the total cfm from the Kitchen exhaust. <br /> Exhaust Schedule, indicate flow in cfm for proposed method(s)of providing make-up air. Other exhaust <br /> Step 5. Fill out the Passive Make-up Air Opening Schedule above. -TOTAL <br /> U Path 0 — Aggregate Make-up Air Method Passive Passive Powered <br /> Infiltration Opening Make-up <br /> Passive infiltration for up to 425 cfm <br /> Passive openings for cfms over 425 <br /> Powered to match flow for cfrns over 985 <br /> ❑ Path 1 — Aggregate Make-up Air Method Passive Passive Powered <br /> Infiltration Opening* Make-up <br /> Passive infiltration up to 175 cfm* <br /> Passive openings for cfms over 175 <br /> Powered to match flow for cfms over 565 <br /> * If a closed controlled solid-fuel burning appliance is installed in Path 1,then a passive opening must be installed to provide make-up <br /> air for the clothes dryer and for any central vacuum that exhausts to the outside. <br /> U Path 2 — Aggregate Make-up Air Method Passive Passive Powered <br /> Infiltration Opening Make-up <br /> Passive openings for up to 175 cfm <br /> Powered to match flow for cfms over 175 N/A <br /> ❑ Path 3 — Aggregate Make-up Air Method Passive Passive . Powered <br /> Infiltration Opening Make-up <br /> Powered to match flow N/A N/A <br /> 16 <br />