<br /> * DITTER, INC. * PROJECT: NEW HOUSE 3/96
<br /> 820 TOWER DRIVE CLIENT: GREG KELLENBERGER
<br /> HAMEL, MN 55340 DATE: 03/ 13/96
<br /> RESIDENTIAL/LIGHT COMMERCIAL HVAC LOADS DESIGNER: DOUG
<br /> CLIENT INFORMATION:
<br /> NAME: GREG KELLENBERGER
<br /> ADDRESS: 4045 WATERTOWN RD.
<br /> CITY, STATE: ORONO, MN.
<br /> TOTAL BUILDING LOADS:
<br /> BLDG. LOAD AREA SEN. IAT. + SEN. = TOTAL
<br /> DESCRIPTIONS QUAN LOSS GAIN GAIN GAIN
<br /> 3-D WINDOW DBL PN LOW EMIT WOOD FR 449 14, 912 0 13, 362 13, 362
<br /> 9-J FRENCH DOOR DBL LOW E WOOD FR 126 3, 964 0 3, 793 3, 793
<br /> 12-L WALL R-19 + R-8 SHEATHING 2, 619 9, 638 0 2; 786 2, 786
<br /> 15-D WALL 2-5' BLW GRD 8/12" BLK+R-19 676 2, 115 0 0 0
<br /> 15-H WALL >5' BELOW GRD 8" BLK+R-19 216 616 0 0 0
<br /> 11-C DOOR METAL POLYSTYRENE CORE 63 2, /24 0 789 789
<br /> 16-I CEILING R-44 INSULATION 1 , 401 2, 965 0 1 , 514 1 , 514
<br /> 21-A BASEMT FLOOR 2' OR> BELOW GRADE 1 , 577 3, 482 0 0 0
<br /> SUBTOTALS FOR STRUCTURE: 7, 127 40, 416 0 22, 244 22, 244
<br /> PEOPLE 6 0 1 , 380 1 , 800 3, 180
<br /> APPLIANCES 0 0 0 1 , 200 1 , 200
<br /> DUCTWORK 0 0 0 0 0
<br /> INFILTRATION W. CFM: 252. 3 S. CFM: 126. 1 0 25, 533 2, 831 3, 192 6, 023
<br /> VENTILATION W. CFM: 75. 0 S. CFM: 75. 0 0 7, 590 1 , 683 1 , 898 3, 581
<br /> SENSIBLE GAIN TOTAL 30, 334
<br /> TEMP. SWING MULTIPLIER X 1 . 00
<br /> BUILDING LOAD TOTALS 73, 539 5, 894 30, 3„1:,4 36, 228
<br /> SUPPLY CFM AT 20 DEG DT: 1 , 293 CFM PER SQUARE FOOT: 0. 284
<br /> SQUARE FT. OF ROOM AREA: 4, 555 SQUARE FOOT PFR TON: 1 , 508. 778
<br /> TOTAL HFATING REQUIRED WITH OUTSIDE AIR: 73. 539 MBH
<br /> TOTAL COOLING REQUIRED WITH OUTSIDE AIR: 3. 019 TONS
<br /> CALCULATIONS ARE BASED ON 7TH EDITION OF ACCA MANUAL J.
<br /> ALL COMPUTED RESULTS ARE ESTIMATES AS BUILDING USE AND WEATHER MAY VARY.
<br /> BE SURE TO SELECT A UNIT THAT MEETS BOTH SENSIBLE AND LATENT LOADS.