Rhvac-Residential&Light Commercial HVAC Loads Elite Software Development,Inc.
<br /> Sabre Plumbing&Heating 780 Lakeview Parkway Orono EVENSON
<br /> Plymouth,MN 55447 Page 4
<br /> Total Building Summary Loads
<br /> Component Area Sen Lat Sen Total
<br /> Description Quan Loss Gain Gain Gain
<br /> Low EE: Glazing-LowEE Builder Grade.31 U-value, .29 677.1 18,264 0 18,077 18,077
<br /> SHGC, Window and Patio Door, u-value 0.31, SHGC
<br /> 0.29
<br /> 11J: Door-Metal-Fiberglass Core 37.8 1,972 0 544 544
<br /> 15A-10sffc-8: Wall-Basement, concrete block wall, R-10 1705.5 6,770 0 150 150
<br /> foam board to floor, no framing, no interior finish,
<br /> filled core, 8'floor depth
<br /> 15A-10sffc-4: Wall-Basement, concrete block wall, R-10 40 174 0 0 0
<br /> foam board to floor, no framing, no interior finish,
<br /> filled core, 4'floor depth
<br /> R20 12F-Osw:Wall-Frame, Custom, R-20 Insulation in 3704.6 21,273 0 3,252 3,252
<br /> 2x6 Cavity, no board insulation, siding finish,wood
<br /> studs
<br /> RJ 20 Spray Foam: Wall-Frame, Custom, Rim Joist R-20 502.5 2,187 0 617 617
<br /> Closed Cell Spray Foam
<br /> R49 16B-49: Roof/Ceiling-Under Attic with Insulation on 2402 4,807 0 2,652 2,652
<br /> Attic Floor(also use for Knee Walls and Partition
<br /> Ceilings),Custom, R-49 Blown Insulation, No
<br /> Radiant Barrier,Vented Attic,Asphalt Shingles
<br /> 21A-20: Floor-Basement, Concrete slab, any thickness, 2 2279 5,354 0 0 0
<br /> or more feet below grade, no insulation below floor,
<br /> any floor cover, shortest sideof floor slab is 20'wide
<br /> Subtotals for structure: 60,801 0 25,292 25,292
<br /> People: 6 1,200 1,380 2,580
<br /> Equipment: 901 4,116 5,017
<br /> Lighting: 1250 4,263 4,263
<br /> Ductwork: 0 0 0 0
<br /> Infiltration:Winter CFM: 0, Summer CFM: 0 0 0 0 0
<br /> Ventilation: Winter CFM: 210, Summer CFM: 210 7,799 4,873 1,165 6,038
<br /> Humidification (Winter)21.96 gaVday : 8,052 0 0 0
<br /> AED Excursion;_..... 0 0... 3 038 3 038
<br /> Total Building Load Totals: 76,652 6,974 39,254 46,228
<br /> Check Figures
<br /> Total Building Supply CFM: 1,784 CFM Per Square ft.: 0.322
<br /> Square ft. of Room Area: 5,540 Square ft. Per Ton: 1,438
<br /> Volume (ft3)of Cond. Space: 57,547
<br /> Building Loads
<br /> Total Heating Required Including Ventilation Air: 76,652 Btuh 76.652 MBH
<br /> Total Sensible Gain: 39,254 Btuh 85 %
<br /> Total Latent Gain: 6,974 Btuh 15 %
<br /> Total Cooling Required Including Ventilation Air: 46,228 Btuh 3.85 Tons (Based On Sensible+ Latent)
<br /> Notes
<br /> Rhvac is an ACCA approved Manual J and Manual D computer program.
<br /> Calculations are performed per ACCA Manual J 8th Edition,Version 2, and ACCA Manual D.
<br /> All computed results are estimates as building use and weather may vary.
<br /> Be sure to select a unit that meets both sensible and latent loads according to the manufacturer's performance data at
<br /> your design conditions.
<br /> Thursday, September 22, 2016, 9:27 AM