Laserfiche WebLink
Total Building Summaty Loads <br /> IN Ij 11111 <br /> IN <br /> 3D Window Double Pane Low Emit Wood Frame 1067 35,437 0 19,206 19,206 <br /> 11C Door Metal Polystyrene Core 63 2,724 0 551 551 <br /> 121 Wall R-19+ 1/2"Asphlt Board(R-1.3) 3739 18,918 0 3,825 3,825 <br /> 15G Wall V or More Below Grade 8/12" BIk+R-11 1197 4,735 0 0 0 <br /> 161 Ceiling R-44 Insulation 2212 4,681 0 1,984 1,984 <br /> 19J Floor Over Basement/Encl Crawl Carpet+ R-30 494 795 0 0 0 <br /> 21A Basemt Floor 2'or More Below Grade 1718 3,793 0 0 0 <br /> Subtotals for structure: 71,083 0 25,566 25,566 <br /> People: 10 2,300 3,000 5,300 <br /> Equipment: 300 1,200 1,500 <br /> Lighting: 0 0 0 <br /> Ductwork: 9,966 0 0 0 <br /> Infiltration: Winter CFM: 266, Summer CFM: 310 26,089 6,528 4,963 11,491 <br /> Ventilation: Winter CFM: 90, Summer CFM: 90 8,837 1,895 1,441 3,336 <br /> Sensible Gain Total: 36,170 <br /> Temperature Swing Multiplier: X 1.15 <br /> Total Building Load Totals: 115,975 11,023 41,595 52,619 <br /> Total Building Supply CFM: 1,871 (2.1 AC/hr) CFM Per Square ft.: 0.331 <br /> Square ft. of Room Area: 5,659 Square ft. Per Ton: 1,257 <br /> lffzffl��� 101111111111 <br /> Total Heating Required With Outside Air: 115,975 Btuh 115.975 MBH <br /> Total Sensible Gain: 41,595 Btuh 79 % <br /> Total Latent Gain: 11,023 Btuh 21 % <br /> Total Cooling Required With Outside Air: 52,619 Btuh 4.38 Tons(Based On Sensible+ Latent) <br /> 4.50 Tons(Based On 77%Sensible Capacity) <br /> Calculations are based on 7th edition of ACCA Manual J. <br /> All computed results are estimates as building use and weather may vary. <br /> Be Sure to select a unit that meets both sensible and latent loads. <br />