Laserfiche WebLink
Miscellaneous Report <br /> IN <br /> Winter: -16 0 50 72 0.00 <br /> Summer: 89 73 50 75 33.54 <br /> ME <br /> Main Trunk Runouts <br /> Calculate: Yes Yes <br /> Use Schedule: Yes Yes <br /> Roughness Factor: 0.00300 0.01000 <br /> Pressure Drop: 0.1000 in.wg./100 ft. 0.1000 in.wg./100 ft. <br /> Minimum Velocity: 650 ft./min 450 ft./min <br /> Maximum Velocity: 900 ft./min 750 ft./min <br /> Minimum Height: 8 in. 6 in. <br /> Maximum Height: 12 in. 8 in. ' <br /> Winter Summer <br /> Infiltration: 0.700 AC/hr 0.400 AC/hr <br /> Volume of Conditioned Space: X 71467 Cu.ft. X 71467 Cu.ft. <br /> 50,027 Cu.ft./hr 28,587 Cu.ft./hr <br /> X 0.0167 X 0.0167 <br /> Total Building Infiltration: 834 CFM 476 CFM <br /> Total Building Ventilation: 50 CFM 50 CFM <br /> --System 1--- <br /> Infiltration &Ventilation Sensible Gain Multiplier: 14.94 = (1.10 X 0.970 X 14.00 Summer Temp. Difference) <br /> Infiltration &Ventilation Latent Gain Multiplier: 22.13 = (0.68 X 0.970 X 33.54 Grains Difference) <br /> Infiltration &Ventilation Sensible Loss Multiplier. 93.92 = (1.10 X 0.970 X 88.00 Winter Temp. Difference) <br /> C:\Elite\Rhvacw\Projects\Vaillant Residence.rhv Wednesday, July 23, 2003, 2:21 PM <br />