S stem 1, Zone 3 Summary Loads <br /> 3D Window Double Pane Low Emit Wood Frame 175 5,558 0 3,607 3,607 <br /> 8P Glass Door Double Low a Wood Frame 120 3,810 0 2,472 2,472 <br /> 11E Door Metal Urethane Core 20 334 _ 0 67 67 <br /> 12H Wall R-19 + 1/2" Gypsum Board(R-0.5) 435 2,297 0 459 459 <br /> 15C Wall 2-5' Below Grade 8/12" BIk+R-11 870 3,903 0 0 0 <br /> 15G Wall 5'or More Below Grade 8/12" BIk+R-11 1240 4,693 0 0 0 <br /> 21A Basemt Floor 2'or More Below Grade 1698 3,586 0 0 0- <br /> 22C Slab on Grade 11/2" Edge Insulation(R_8� — _ _ 1.1_7 2,779 0 0 0 <br /> Subtotals for structure: 26,960 0 6,605 6,605 <br /> People: 2 460 600 1,060 <br /> Equipment: 0 0 0 <br /> Lighting: 0 0 0 <br /> Ductwork: 0 0 0 0 <br /> Infiltration: Winter CFM: 163, Summer CFM: 93 15,283 2,057 _1,389 3,446 <br /> Sensible Gain Total: 8,594 <br /> TeTerature Swing Multiplier: X 1.00 <br /> System 1, Zone 3 Load Totals: 42,243 2,517 8,594 11,111 <br /> ELVIM <br /> Supply CFM: 403 (0.8 AC/hr) CFM Per Square ft.: 0.131 <br /> Square ft. of Room Area: 3,077 Square ft. Per Ton: 2,791 <br /> Total Heating Required: 42,243 Btuh 42.243 MBH <br /> Total Sensible Gain: 8,594 Btuh 77 % <br /> Total Latent Gain: 2,517 Btuh 23 % <br /> Total Cooling Required: 11,111 Btuh 0.93 Tons(Based On Sensible+ Latent) <br /> 1.10 Tons(Based On 75% Sensible Capacity) <br /> Calculations are based on 7th edition of ACCA Manual J. <br /> All computed results are estimates as building use and weather may vary. <br /> Be sure to select a unit that meets both sensible and latent loads. <br /> C:\Elite\Rhvacw\Projects\Vaillant Residence.rhv Wednesday, July 23, 2003, 2:21 PM <br />