GENERAL NOTES:
<br />A> THE SCOPE OF THIS JOB IS AS FOLLOWS:
<br />NEW ADDITION
<br />FURNISH & INSTALL NEW FURNACE F-1 & F-2 WITH AIR CONDITIONING UNITS C-1 & C-2 & ASSOCIATED
<br />DUCTWORK.
<br />FURNISH & INSTALL EF -3, EF -4 & EF -5 & ASSOCIATED DUCTWORK TO SERVE THE RESTROOMS.
<br />FURNISH ONLY ELECTRIC HEATERS EH -1 THRU EH -5.
<br />EXISTING BUILDING
<br />THE EXISTING 105,000 BTU/H FURNACE SERVING THE PRIVATE QUARTERS TO REMAIN.
<br />REPLACE THE EXISTING FURNACE SERVING THE DINING HALL WITH A NEW MAKE UP AIR UNIT (MUA-1). MUA-1
<br />WILL SERVE THE DINING HALL/KITCHEN ON THE MAIN LEVEL, THE ACTIVITY ROOM & STORAGE AREAS ON THE
<br />LOWER LEVEL & PROVIDE MAKE UP AIR TO THE KITCHEN ON THE MAIN LEVEL. UTILIZE THE EXISTING DUCTWORK
<br />TO THE EXTENT PRACTICAL. RUN NEW GAS PIPING TO MUA-1. PROVIDE TRANSFER GRILLES BETWEEN THE DINING
<br />HALL & THE KITCHEN. MUA-1 TO DELIVER 100% OUTSIDE AIR DURING OCCUPIED HOURS & 0% OUTSIDE AIR
<br />DURING UNOCCUPIED HOURS.
<br />REPLACE THE EXISTING KITCHEN HOOD WITH NEW HOOD H-2, REPLACE THE EXISTING KITCHEN HOOD EXHAUST FAN
<br />WITH EF -2. REPLACE THE EXISTING GALVANIZED GREASE DUCT WITH WELDED 16 GAUGE BLACK IRON,
<br />FURNISH & INSTALL NEW DISHWASHER HOOD (H-1) & EXHAUST FAN (EF -1) & NEW ALUMINUM EXHAUST
<br />DUCTWORK.
<br />FURNISH & INSTALL NEW COMBUSTION AIR DUCTWORK TO THE EXISTING WATER HEATERS & EXISTING FURNACE.
<br />B> INSTALL DUCTWORK PER SMACNA, UMC & LOCAL CODES.
<br />C> KITCHEN HOOD EXHAUST DUCTWORK FROM TYPE I HOODS TO BE 16 GAUGE WELDED BLACK IRON DUCT.
<br />PROVIDE CLEAN OUTS AS REQUIRED. DISHWASHER EXHAUST DUCTWORK TO BE ALUMINUM.
<br />D> PROVIDE VOLUME DAMPERS AT DUCT TAKE OFFS TO DIFFUSERS. SIZE DUCT RUN OUTS TO DIFFUSERS TO
<br />MATCH NECK SIZE FOR CFM INDICATED IN DIFFUSER SCHEDULE.
<br />E> VENTILATION AIR REQUIREMENTS ARE BASED ON ASHRAE 62-1999 AS FOLLOWS:
<br />ANTICIPATED DINING ROOM OCCUPANCY: 88 PEOPLE, ANTICIPATED DINING ROOM OCCUPANCY DURATION: LESS
<br />THAN THREE HOURS, THE OUTSIDE AIR REQUIREMENTS PER PERSON PER TABLE 2 OF ASHRAE 62-1999 FOR
<br />DINING AREAS:20 CFM. OUTSIDE AIR REQUIRED CAN BE REDUCED BY HALF IF THE OCCUPANCY DURATION IS LESS
<br />THAN THREE HOURS, THEREFORE THE OUTSIDE AIR REQUIREMENTS ARE 88 PEOPLE x 20 CFM/PERSON x 1/2 =
<br />880 CFM. THE OUTSIDE AIR REQUIREMENT WILL BE SATISFIED BY MUA-1 WHICH WILL INTRODUCE 2,700 CFM OF
<br />OUTSIDE AIR TO BALANCE THE KITCHEN EXHAUST REQUIREMENTS. THE DINING AREA WILL BE SUPPLIED WITH A
<br />MINIMUM OF 880 CFM TO SATISFY THE OUTSIDE AIR REQUIREMENTS FOR THE OCCUPANTS.
<br />F> NEW HVAC ITEMS SHOWN AS DARK CONTINUOUS LINES. EXISTING HVAC ITEMS SHOWN AS DASHED LINES.
<br />G> VERIFY THERMOSTAT LOCATIONS WITH OWNER PRIOR TO INSTALLATION,
<br />H> THE UPPER & LOWER LEVELS OF THE NEW ADDITION ARE TO HAVE A DRYWALL CEILING, EXCEPT A LAY IN
<br />CEILING WILL BE INSTALLED IN THE HALLWAYS & STAIRWAY.
<br />GAS METER
<br />MPLS GAS CO, METER #i 282234 -� n_. __. _....____..___..._____.v ................
<br />._.n....._,__...__...__.__.. _.........._......
<br />u
<br />1
<br />i
<br />6"0 FLUE
<br />1
<br />NEW WATER HEATER COMBUSTION AIR DUCT
<br />k
<br />EXISTING WATER HEATER
<br />MAKE: BOCK MODEL: 50G -115S
<br />125,000 BTU/H INPUT
<br />10"0
<br />COMBUSTION AIR THRU WALL
<br />1-120
<br />1-120
<br />AHU-1
<br />EXISTING CONDENSING UNIT SERVING THE KITCHEN
<br />24/16 DUCT THRU EXISTING WALL OPENING
<br />J
<br />r;
<br />STORAGE ARES+ SERVED BY MUA-1
<br />SUPPLY 350 CFM TO THE STORAGE AREAS
<br />REMOVE EXISTING F
<br />50,000 BTU/H MINIMUM INPUT
<br />300,000 MAXIMUM INPUT
<br />10-0,000 BTU/H EFFECTIVE INPUT
<br />400 RECONNECT EXISTING ;SUPPLY- &- RETURN
<br />DUCTING TO NEW MUA--1, PRQVIDE DAMPERS IN
<br />;THE RETURN DUCT & OUTSIDI= AIR DUCT S❑
<br />•CHAT 100% OUTSIDE AIR IS SUP,- ILD DURING
<br />:OCCUPIED HOURS & 100% RETURN AIR IS USED
<br />DURING UNOCCUPIED jtluumS
<br />35/10
<br />CL_..
<br />' 71c,
<br />THREE 4"0 FLUES UP EXISTING 10.5"x10,5" CHIMNEY
<br />I m I
<br />IMI ,
<br />7
<br />I I
<br />EXISTING RETURN DUCT TO GRILLES ON UPPER LEVEL - TYPICAL
<br />— -I
<br />EXISTING RETURN DUCTWORK �I
<br />IMI
<br />EH_2Lo
<br />....
<br />� I
<br />__ ........
<br />,' r,
<br />.. ..., .. ..., ..-.,._. ,... ..a.,.,._.. _ _ ..
<br />t _Y
<br />4 S1 -14Q
<br />NEW COMBUSTION AIR DUCT TO
<br />SERVE EXISTING FURNACE &
<br />WATER HEATER
<br />�0� I
<br />610
<br />L J EXISTING 34,OOQ BTU/H WATER HEATER
<br />EXISTING 105,000 B'f U7H INPUT FURNACE TO REMAIN
<br />EXISTING 22,000 BTU/H INPUT GAS DRYER
<br />NOTE: DUCTWORK FOR LOWER LEVEL TO BE RUN IN
<br />THE FLOOR TRUSS SPACE, FLOOR TRUSSES 16" DEEP &
<br />ca
<br />�I
<br />,
<br />19.2" 0,C.
<br />i
<br />I fes. = _ = -, cu 9 A 7 n-._._171 [-I I ,
<br />MAKE UP AIR UNIT SCHEDULE
<br />ITEM
<br />MAKE MODEL
<br />INPUT
<br />(BTUH)
<br />OUTPUT A.F,U,E,
<br />(BTUH) (�)
<br />FLUE
<br />DIAMETER
<br />(INCHES)
<br />AIRFLOW
<br />ELECTRICAL
<br />WEIGHT
<br />(LBS)
<br />REMARKS
<br />(CFM)
<br />ESP
<br />(IN WC)
<br />VOLTS
<br />BREAKER
<br />(AMPS)
<br />PHASE
<br />HERTZ HP
<br />AHU-1
<br />STERLING AH2O00M
<br />---
<br />--- ---
<br />---
<br />2,700
<br />---
<br />208/230
<br />---
<br />1
<br />60 3.0
<br />---
<br />INTERL❑CK TO EF -1 & EF -2
<br />DF -1
<br />STERLING OVES150M
<br />150,000
<br />120,000 80
<br />4
<br />2,700
<br />---
<br />115
<br />---
<br />1
<br />60 ---
<br />---
<br />POWER VENT, STAINLESS STEEL HEAT EXCHANGER
<br />DF -2
<br />STERLING QVSD150A2N2AD
<br />150,000
<br />120,000 80
<br />4
<br />2,700
<br />---
<br />115
<br />---
<br />1
<br />60 ---
<br />---
<br />POWER VENT, STAINLESS STEEL HEAT EXCHANGER, MECHANICAL MODULATI❑N GAS VALVE
<br />DF -3
<br />STERLING QVSD150A1N2AK
<br />150,000
<br />120,000 80
<br />4
<br />2,700
<br />---
<br />115
<br />---
<br />1
<br />60 ---
<br />---
<br />POWER VENT, ALUMINIZED HEAT EXCHANGER, 2 STAGE GAS VALVE
<br />ELECTRIC HEATER SCHEDULE
<br />ITEM
<br />MAKE/MODEL WATTS
<br />BTUH
<br />VOLTS AMPS
<br />PHASE
<br />HERTZ
<br />AREA
<br />SERVED
<br />REMARKS
<br />EH -1
<br />QMARK CDF548SE 4,000
<br />13,700
<br />240 19,2
<br />1
<br />60
<br />CORRIDOR
<br />CEILING MOUNTED
<br />EH -2
<br />QMARK CDF548SE 4,000
<br />13,700
<br />240 19,2
<br />1
<br />60
<br />CORRID❑R
<br />CEILING MOUNTED
<br />EH -3
<br />QMARK CDF548SE 4,000
<br />13,700
<br />240 19,2
<br />1
<br />60
<br />CORRID❑R
<br />CEILING MOUNTED
<br />EH -4
<br />QMARK CDF548SE 4,000
<br />13,700
<br />240 19,2
<br />1
<br />60
<br />1 STAIRWAY
<br />CEILING MOUNTED
<br />EH -5
<br />QMARK FZ1504 1,500
<br />5,120
<br />240 1 6.3
<br />1
<br />60
<br />STORAGE
<br />SURFACE WALL MOUNTED AS HI AS PRACTICAL
<br />NOTE: ELECTRIC HEATER FURNISHED BY THERMEX, INSTALLED BY ELECTRICAL CONTRACTOR
<br />u
<br />FIRE/SMOKE DAMPER SCHEDULE
<br />ITEM ID
<br />SIZE
<br />(INCHES)
<br />REMARKS
<br />FSD-1
<br />8"x8"
<br />CEILING SUPPLY REGISTER
<br />FSD-2
<br />8"x8"
<br />S2
<br />LOVER LEVEL HVAC PLAN
<br />SCALE: 1/8"=1'-0"
<br />mi
<br />DIFFUSER, REGISTER & GRILLE SCHEDULE
<br />TYPE
<br />AIR FLOW NECK FACE
<br />(CFM) SIZE SIZE
<br />MAKE/MODEL/TYPE/REMARKS
<br />Sl
<br />0-115 6"0 10"x10"
<br />CEILING SUPPLY REGISTER
<br />116-250 8"o 10"x10"
<br />251-440 10"0 10"x10',
<br />S2
<br />0-125 --- 8"x8"
<br />WALL SUPPLY REGISTER
<br />R1
<br />0-11000 --- 12"x12"
<br />CEILING RETURN GRILLE
<br />R2
<br />0-100 --- 8'x8'
<br />RETURN GRILLE
<br />735 16' x18"
<br />T
<br />0-310 --- 12"x12"
<br />TRANSFER GRILLE
<br />1,350 --- 36x18"
<br />� v o
<br />c
<br />'C v
<br />O =
<br />0 c i o
<br />O�Q t\2 Lo U
<br />U CD
<br />L ~
<br />:cQ Lo o �. o
<br />O c v) -0 v
<br />U
<br />a) o m co
<br />c v 1,0�
<br />p L_1 A o o
<br />- p ol o c,
<br />W c°;o^
<br />c0 � c-2
<br />_� co
<br />rn p cz 'v�
<br />•� :.42
<br />C Lo E -W
<br />�
<br />t �
<br />w°' c
<br />= w
<br />L 4- -p m
<br />0 W }
<br />o 'v c
<br />T V O
<br />.2 EJ 3
<br />L
<br />CL c -v m
<br />N 3 S
<br />v y-
<br />L
<br />v ° E a
<br />°' °)° o
<br />N E_ c
<br />v m
<br />_ W c
<br />a c
<br />N c v -
<br />U 0 0
<br />C •- .2
<br />•j N O
<br />N
<br />i 0
<br />aao0
<br />m 7 L a
<br />L VI O_ y
<br />,7Z
<br />Nei
<br />ISSUE FOR PERMIT
<br />t4 C) f rn'1
<br />DRAWN BY: MH
<br />Lr)
<br />to
<br />co
<br />rn
<br />0
<br />z
<br />c
<br />0
<br />a
<br />y
<br />m
<br />M
<br />0
<br />0
<br />N
<br />N
<br />1-11N
<br />v
<br />O
<br />CHECKED BY:CURT BREKKE
<br />JOB #: 70236
<br />M1
<br />SHEET 1 OF 2
<br />Z
<br />F-
<br />�_
<br />0
<br />O
<br />p
<br />U
<br />O
<br />Q
<br />rill
<br />Q
<br />J
<br />°6
<br />Q
<br />_
<br />z
<br />o
<br />Lo
<br />a
<br />z
<br />u
<br />pz
<br />oo
<br />z
<br />>
<br />W
<br />aw
<br />Z
<br />Z?
<br />ci
<br />0
<br />o
<br />.72
<br />Q
<br />I- Z
<br />Q
<br /><t
<br />=
<br />0
<br />W
<br />U
<br />U
<br />(o o
<br />=
<br />ISSUE FOR PERMIT
<br />t4 C) f rn'1
<br />DRAWN BY: MH
<br />Lr)
<br />to
<br />co
<br />rn
<br />0
<br />z
<br />c
<br />0
<br />a
<br />y
<br />m
<br />M
<br />0
<br />0
<br />N
<br />N
<br />1-11N
<br />v
<br />O
<br />CHECKED BY:CURT BREKKE
<br />JOB #: 70236
<br />M1
<br />SHEET 1 OF 2
<br />
|