<br /> , R C Residential&Light Commercial HVAG Loads Program , Elite Software Development,Inc.
<br /> Ditta,Inc. ` JENKINS "
<br /> H��el,MN 55340-9691 #�age 2
<br /> Total Building Summary Loads
<br /> Component Area Sen. Lat. Sen. Total
<br /> Description Quan Loss Gain Gain Gain
<br /> 3A Window Double Pane Clear Glass Wood Frame 220 11,152 0 11,312 11,312
<br /> 10F Door Wood Solid Core& Metal Storm 63 1,854 0 477 477
<br /> 12C Wall R-11 + 1/2" Gypsum(R-0.5) 1,621 13,422 0 3,443 3,443
<br /> 12D Wall R-11 + 1/2"Asphlt Board(R-1.3) 1,248 9,186 0 2,356 2,356
<br /> 16G Ceiling R-30 Insulation 1,512 4,590 0 2,195 2,195
<br /> 21A Basemt Floor 2'or More Below Grade 1,512 3,338 0 0 0
<br /> Subtotals for structure: 6,176 43,542 0 19,783 19,783
<br /> Active People: 6 0 1,380 1,800 3,180
<br /> Inactive People: 0 0 0 0 0
<br /> Appliances: 0 0 0 1,200 1,200
<br /> Lighting: 0 0 0
<br /> Ductwork: 0 0 0 0 0
<br /> Infiltration: Winter CFM: 302.4, Summer CFM: 181.4 283 29,692 4,308 3,873 8,181
<br /> Ventilation: Winter CFM: 0.0, Summer CFM: 0.0 0 0 0 0 0
<br /> Sensible Gain Total: 26,656
<br /> Temperature Swing Multiplier: X1.00
<br /> Building Load Totals: 73,234 5,688 26,656 32,344
<br /> Check Figures'
<br /> Total Building Supply CFM: 1249 CFM per square foot: 0.826
<br /> Square feet of room area: 1,512 Square feet per ton: 510.504
<br /> Building Loads
<br /> Total heating required with outside air: 73,234 Btuh 73.234 MBH
<br /> Total sensible gain: 26,656 Btuh 82 %
<br /> Total latent gain: 5,688 Btuh 18 %
<br /> Total cooling required with outside air: 32,344 Btuh 2.695 Tons(based on sensible+latent)
<br /> 2.962 Tons (based on 75% sensible capacity)
<br /> Notes
<br /> Calculations are based on 7th edition of ACCA Manual J.
<br /> All computed results are estimates as building use and weather may vary.
<br /> Be sure to select a unit that meets both sensible and latent loads.