UPue. . g,,toys "
<br /> tit V ; DN-7070:P•A-10
<br /> NFS2-3030 NOTIFIER®
<br /> Intelligent Addressable
<br /> Fire Alarm System by Honeywell
<br /> Intelligent Fire Alarm Control Panels
<br /> General
<br /> The NFS2-3030 is an intelligent Fire Alarm Control Panel
<br /> (FACP) designed for medium- to large-scale facilities. Fire
<br /> emergency detection and evacuation are extremely critical to
<br /> life safety,and the NFS2-3030 is ideally suited for these appli- { 111
<br /> cations.The NFS2-3030 is part of the ONYX®Series of prod-
<br /> ucts
<br /> rod ucts from NOTIFIER.The NFS2-3030 is ideal for virtually any "'
<br /> application because it features a modular design that is config l– — i °j €,
<br /> ured per project requirements.With one to ten Signaling Line ° s
<br /> Circuits (SLCs), the NFS2-3030 supports up to 3,180 intelli = i _,
<br /> gent addressable devices.
<br /> Information is critical to fire evacuation personnel, and the
<br /> NFS2-3030's large 640-character Liquid Crystal Display(LCD)
<br /> presents vital information to operators concerning a fire situa-
<br /> tion,fire progression,and evacuation details.
<br /> A host of other options are available, including single-or multi-
<br /> channel voice;firefighter's telephone; LED, LCD, or PC-based
<br /> graphic annunciators; networking; advanced detection prod- 707oco g.ipg
<br /> ucts for challenging environments;wireless fire protection;and
<br /> many additional options. NFS2-3030 (left)
<br /> Features and NFS2-3030 with DVC audio option (right)
<br /> • Certified for seismic applications when used with the appro-
<br /> priate seismic mounting kit. • With built-in Degraded Mode operation,the system is capa-
<br /> • Approved for Marine applications when a marine listed ver ble of general alarm if a fire alarm condition is present even
<br /> sion is used with marine-listed compatible equipment. See if the central processing unit(CPU)fails.
<br /> DN-60688. • Weekly Occupancy Schedules allow changing sensitivity by
<br /> • Complies with UL 2572 Mass Notification Systems (NFS2 time of day and day of week.
<br /> 3030 version 20 or higher). • EIA-485 annunciators,including custom graphics.
<br /> • One to ten isolated intelligent Signaling Line Circuits(SLC) • History file with 4000-event capacity in nonvolatile memory,
<br /> Style 4,6 or 7. plus separate 1000-event alarm-only file.
<br /> • Wireless fire protection using SWIFT Smart Wireless Inte- • Advanced history filters allow sorting by event, time, date,
<br /> grated Fire Technology.See DN-60820. or address.
<br /> • Up to 159 detectors and 159 modules per SLC;318 devices • Alarm Verification selection per point, with automatic
<br /> per loop/3,180 per FACP or network node. counter.
<br /> –Detectors can be any mix of ion, photo,thermal, or multi- • Autoprogramming and Walk Test reports.
<br /> sensor; wireless detectors are available for use with the • Multiple central station communication options:
<br /> FWSG. –Standard UDACT
<br /> –Modules include addressable pull stations, normally open –Internet
<br /> contact devices,two-wire smoke detectors, notification,or
<br /> –Internet/GSM
<br /> relay; wireless modules are available for use with the
<br /> FWSG. • Positive Alarm Sequence(PAS) Presignal.
<br /> • Large 16 line, 640 character LCD backlit display or use • Silence Inhibit and Auto Silence timer options.
<br /> display-less as a network node. • Field-programmable on panel or on PC, with VeriFire Tools
<br /> • Network options: program,also check,compare.
<br /> –High-speed network for up to 200 nodes (NFS2-3030, • Non-alarm points for lower priority functions.
<br /> NFS2-640, NFS-320(C), NFS-320SYS, NCA-2, DVC-EM, • Remote ACK/Signal Silence/System Reset/Drill via monitor
<br /> ONYXWorks,NFS-3030, NFS-640,and NCA). modules.
<br /> –Standard network for up to 103 nodes (NFS2-3030, • Up to 1000 powerful Boolean logic equations.
<br /> NFS2-640, NFS-320(C), NFS-320SYS, NCA-2, DVC-EM, . Supports SCS Series smoke control system in both HVAC
<br /> ONYXWorks,NCS, NFS-3030, NFS-640,NCA,AFP-200, and FSCS modes.
<br /> AFP 300/400, AFP 1010, and AM2020). Up to 54 nodes • FM6320 approved Gas Detection System with FMM-4-20
<br /> when DVC-EM is used in network paging. module and any FM listed gas detector.
<br /> • Built-in Alarm,Trouble,Security,and Supervisory relays. • EIA 232 printer port.
<br /> • VeriFire®Tools online/offline program option. • EIA 485 annunciator port.
<br /> DN-7070:P•3/8/17—Page 1 of 8