Laserfiche WebLink
Job Name: Drawing1 <br /> Remote Area Number: 1 Date: 5/23/2018 <br /> Pipe Information <br /> Elev 1 Flow added Fittings& Length C Factor Total(Pt) Notes <br /> Node 1 (Foot) K-Factor this step Nominal ID Devices (Foot) FittinglDevice(Equivalent <br /> (9) Fitting Length) <br /> Pf Friction Elev(Pe) Fixed Pressure Losses,when <br /> Elev 2 Total Flow Equiv. (Foot) Loss Per Unit - applicable,are added directly <br /> Node 2 Actual ID Length Total <br /> (Foot) (Q) (Foot) (Foot) (psi) <br /> Friction(Pf) to(Pf)antd shown as a <br /> nega <br /> e <br /> 100 10'-0" 4.9 16.97 1 (See 15'-0" 150 12.000 Route 1 <br /> Notes) Sprinkler, <br /> 8'-0" -0.434 <br /> 10 11'-0" 16.97 1.10 0.050231 — E(7'-0"),Tr(1'-0") <br /> 23'-0" 1.155 <br /> 10 11'-0" 17.55 1 (See 49'-11" 150 12.722 <br /> Notes) Flow(q)from Route 2 <br /> 19'-0" <br /> 11 11'-0" 34.53 1.10 0.186851 — 4Tr(1'-0"),C(5'-0"),21(5'-0") <br /> 68'-11" 12.878 <br /> 11 11'-0" 11/4 (See 21'-6'/2" 150 25.599 <br /> Notes) 18'-0" 3.035 <br /> 4 4'-0" 34.53 1.39 " 0.059216 — Tr(1'-0"),2E(8'-0"),cplg(1'-0") <br /> 39'-6/2 2.343 <br /> 4 4'-0" 1% (See 7'-9" 120 30.977 <br /> Notes) 22'-0" 1.734 <br /> 2 0'-0" 34.53 1.38 0.093988 - 2BaIV,2T(6'-0"),sCV(7'-0"), <br /> 29'-9" 2.796 E(3'-0") <br /> 2 34.53 Pump 35.507 <br /> Rating:0.000 @ 0.00 <br /> 1 — Churn Pressure: 72.000 <br /> 0.00 35.507 Hose Allowance At Source <br /> 2 34.53 Total(Pt) Route 1 <br /> 101 10'-0" 4.9 17.55 1 (See 1'-0" 150 12.835 Route 2 <br /> Notes) Sprinkler, <br /> 5'-0" -0.434 <br /> 10 11'-0" 17.55 1.10 6'-0" 0.053454 0.321 <br /> 1(5'-0") <br /> 12.722 Total(Pt) Route 2 <br /> &,©M.E.P.CAD,Inc. in AutoSPRINK®12 v12.1.1.0 1 5/23/2018 7:02:53AM Page 5 <br />