Laserfiche WebLink
., . <br /> dB Summary Of Outflowing DevicesIIJob Number: 1 <br /> Report Description:Residential(1) <br /> Actual Flow Minimum Flow K-Factor ! Pressure Density Coverage <br /> Device (gpm) (gpm) (K) (psi) (gpmpft2) (Foot) <br /> c'> Sprinkler 100 16.97 _ 16.97 4.9 12.000 ' 0.052gpm/ft2 324ft2 <br /> Sprinkler 101 17.55 16.97 4.9 12.835 0.054gpm/ft2 324ft2 <br /> b Most Demanding Sprinkler Data <br /> [M,©M.E.P.CAD, Inc. ,;?-4AutoSPRINK®12 v12.1.1.0 5/23/2018 7:02:48AM Page 3 <br />