az'leg® TRUSTED WORLDWIDE SINCE 1908 <br /> CONTROLLER <br /> I - Controller shall be an NFPA 13D panel designed to start <br /> and stop an NFPA 13D Fire Pump based on system pressure. <br /> The Controller shall be specifically designed to work with <br /> k pump motors that include an integrated pressure switch. The <br /> controller shall not require its own pressure sensing devise. <br /> Controller shall be either a Darley Standard StarterPaq <br /> Controller or a Darley Self-Testing Starterpaq Controller. <br /> STANDARD CONTROL PANEL <br /> ► NEMA 2 Red Enclosure <br /> 2HP Skid Mounted System.Manufacturer's 10. Motor HP rated Disconnect <br /> design subject to change. ► Integrated Minimum Run Timer <br /> ► Integrated Restart Time Delay <br /> PRE-ASSEMBLED DISCHARGE MANIFOLD ► Power Available Light located on panel exterior <br /> ► Failure to start audible and visual alarm <br /> Factory assembled and pressure tested manifold ► Shall include contract for remote start(flow switch or <br /> shall be included with the StarterPaq ES2 or ES3 push button) <br /> Manifold shall feature: ► Dry contact shall be provided to initiate an audible alarm, <br /> ► Grooved Lock style coupling, standard pipe typically used with leak detection sensor <br /> couplings are not allowed SELF TESTING CONTROL PANEL <br /> ► Brass Spring Loaded Check Valve <br /> ► <br /> 1" Female NPT port for Flow Switch, Flow Switch <br /> Darley Self-Testing Control Includes same characteristics as <br /> optional and if used shall be provided by others <br /> Standard Control plus: <br /> 110Test Drain Ball Valve (Brass) <br /> 10. 'A" Pressure Gauge Liquid Filled with 1/4" 0. Additional test timer and terminals for an external test <br /> Isolation Valve solenoid valve <br /> lb. Panel will be set so to conduct a weekly automatic test <br /> ► '/a" Pressure Sensing Line pre-connected to <br /> Integrated Pressure Switch and shall include an on the system <br /> isolation valve <br /> ► 11/4" Female NPT System Connection <br /> ► When a Self—Testing Control Panel is selected the <br /> • <br /> discharge manifold system shall include a '/2" N.C. -44 <br /> solenoid valve <br /> SKID MOUNT N «; <br /> StarterPaq Pump and Panel can mount to the <br /> compact Skid Mount, including electrical and <br /> sensing line connections. The skid base is 14" x 28" <br /> and the panel mount is 36" tall. <br /> LEARN MORE <br /> ootir #DemandDarley ON STARTERPAQ.COM <br /> 1.800.4.DARLEY • DARLEY.COM • (i f1 8- <br />