. , <br /> J Summary Of Outflowing Devices Job Number: 1 <br /> Report Description: Residential(4) <br /> Actual Flow Minimum Flow K-Factor Pressure Density Coverage <br /> Device (gpm) (gpm) (K) (psi) (gpmpft2) (Foot) <br /> c> Sprinkler 303 12.96 12.96 4.9 7.000 0.051gpm/ft' 256ft2 <br /> Sprinkler 318 13.66 12.96 4.9 7.770 0.053gpm/ft2 256ft2 <br /> 14> Most Demanding Sprinkler Data <br /> (M©M.E.P.CAD, Inc. 1.AutoSPRINK®12 v12.1.1.0 5/23/2018 7:05:42AM Page 3 <br />