Laserfiche WebLink
. . <br /> gg Summary Of Outflowing Devices Job Number: 1 <br /> Report Description:Residential(3) <br /> Actual Flow Minimum Flow K-Factor Pressure Density Coverage <br /> Device (gpm) (gpm) (K) (psi) (gpmpft2) (Foot) <br /> • <br /> Sprinkler_ 340 12.99 _ 12.96 4.9 7.027 0.051gpm/ft2 256ft2 <br /> c> Sprinkler 341 12.96 12.96 4.9 7.000 0.051gpm/ft2 256ft2 <br /> c> Most Demanding Sprinkler Data <br /> LM,©M.E.P.CAD, Inc. ,0 AutoSPRINK®12 v12.1.1.0 5/23/2018 7:04:52AM Page 3 <br />