Laserfiche WebLink
ill Summary Of Outflowing Devices Job Number:1 <br /> Report Description:Residential(2) <br /> Actual Flow Minimum Flow K-Factor Pressure Density Coverage <br /> Device (gpm) (gpm) (K) (psi) (gpmpft2) (Foot) <br /> Sprinkler 376 17.08 16.97 4.9 12.155 0.053gpm/ft2 324ft2 <br /> c> Sprinkler 377 16.97 16.97 4.9 12.000 0.052gpm/ft2 324ft2 <br /> b Most Demanding Sprinkler Data <br /> ,©M.E.P.CAD, Inc. 1-4 AutoSPRINK®12 v12.1.1.0 5/23/2018 7:03:56AM Page 3 <br />