Laserfiche WebLink
Svstem Specifications <br /> 1. There may be an issue with maximum tank depth if the existing <br /> plumbing is leaving the house under the footing. If the new tanks <br /> are�going to be buried over 4' deep the cover will need to be <br /> reinforced, approval will have to be given by the inspector, and the <br /> plastic risers will need to be wrapped with smooth plastic. <br /> 2. The force main will need to be protected from freezing under the <br /> driveway. <br /> 3. The force main may need to be air tested if it passes too close to <br /> the existing well. <br /> An "Effluent Filter" is to be installed in the outlet of the second tank. It <br /> should be easily accessible from the ground surface for cleaning. The <br /> effluent filter will be equipped with an alarm. <br /> All run-off water is to be diverted away from the tanks and drainfield <br /> areas <br /> Plastic bolt down manhole covers are to be used and left at grade level <br /> for maintenance access. <br /> Pressure rate glue joint fittings must be used. <br /> If the septic tanks are less than 3' deep the covers are to be insulated <br /> with 2" hi -densit,y foam <br /> � c�a�1� �s �- <br /> US� �- � � � V�o1vvv�. <br /> � � � <br />