2A-a-o: Glazing-Double pane low-e(e=0.60), operable 1181.8 57,200 0 40,106 40,106
<br /> window,wood with metal clad frame
<br /> 11 N: Door-Poiystyrene Care 48 1,478 0 420 420
<br /> 15A11-Oocw-8: Wall-Basement, , framing with R-11 siU to 1720 8,840 0 260 260
<br /> floor in 2 x 4 cavity, open core, no board insulation,
<br /> plus interior finish, wood studs, 8'floor depth
<br /> 12E-Obw: Wall-Frame; R-19 insulation in 2 x 6 stud 410 2,453 0 290 290
<br /> cavity, no board insulation, brick finish,wood studs
<br /> 12E-Osw: Watl-Frame, R-19 insulation in 2 x 6 stud 5503.2 32,930 0 6,138 6,138
<br /> caviry, no boafd insulation, siding finish, wood studs
<br /> 16C�44: Roof/Ceiling-Under attic or knee waA, Vented 3793 7,343 0 3,255 3,255
<br /> Attic, No Radiant Barrier, White or Light Color
<br /> Shingles, Any Wood Shake, Light Metal, Tar and
<br /> Gravel or Membrane, R-44 insulation
<br /> 21A-28: Floor-Basement, Concrete s{ab, any thickness, 2 3204 6,203 0 0 0
<br /> or more feet below grade, no insulation below floor,
<br /> any floor cover, shortest side of floor slab is 28'wide
<br /> 20P-3�: Floor-Over apen crawl space or garage, Passive, 665 1,756 0 180 160
<br /> R-38 blanket insufation, a�cover
<br /> Subtotals for structure: 118,203 0 50,649 50,649
<br /> People: 16 3,680 4,800 8,480
<br /> Equipment: 300 1,200 1,500
<br /> Lighting: 0 0 0
<br /> DuCtwork: 0 0 0 0
<br /> Infiltration:Winter CFM: 378, Summer CFM: 197 35,466 4,358 2,943 7,301
<br /> Ventilation: Winter CFM: 335, Summer CFM: 335 31,463 7,414 5,005 12,419
<br /> Total Building Load Totals: 185,132 15,752 64,597 80,349
<br /> Total Building 5upply CFM: 2,792 CFM Per Square ft.: 0.274
<br /> Square ft. of Room Area: 10,201 Square ft. Per Ton: 1,459
<br /> Volume (ft3) of Cond. Space: 99,819 Air Turnover Rate(per hour): 1.7
<br /> Total Heating Required With OutsideAir. 185,132 Btuh 185.132 MBH
<br /> Total Sensible Gain: 64,597 Btuh 80 %
<br /> Totat Latent Gain: 15,752 Btuh 20 %
<br /> Total Cooling Required With Outside Air: 80,349 Btuh 6.70 Tons(Based On Sensible+ Latent)
<br /> 6.99 Tons(Based On 77%Sensib)e Capacity)
<br /> Calculations are based on 8th edition of AGCA Manuat J.
<br /> All computed results are estimates as building use and weather may vary.
<br /> Be sure to select a unit that meets both sensible and latent loads.