CMP Part 4C. Water Supply <br /> rtcti. V <br /> Population 2'200 2,400 2,600 2,800 3,000 <br /> (Existing) <br /> Fire Demand(gpm)' 2,000 2,000 2,000 2,000 2,000 <br /> Max.Day Demand(gpm) 421 459 498 536 574 <br /> Peak Usage(gpm) 2,421 2,459 2,498 2,536 2,574 <br /> Firm Pumping Supply(gpm)2 500 500 500 500 500 <br /> Withdrawal from Storage(gpm) 1,921 1,959 1,998 2,036 2,074 <br /> Fire Flow Duration(hrs) 3 3 3 3 3 <br /> Fire Demand Storage(gallons) 345,780 352,620 359,640 366,480 373,320 <br /> Emergency Storage(gallons)3 121,248 132,192 143,424 154,368 165,312 <br /> Total Storage Needed(gallons) 467,028 484,812 503,064 520,848 538,632 <br /> Current Available Storage(gallons) 200,000 200,000 200,000 200,000 200,000 <br /> Net Storage Surplus/Deficit(gallons) -267,028 -284,812 -303,064 -320,848 -338,632 <br /> (1)Fire flow requirements vary within the City depending on type and construction of facilities. Fire flow <br /> requirements for normal residential development vary between 1,000 to 1,500 gpm. For multi-family and <br /> commercial areas such as the downtown business district,residential apartment areas,school and industrial <br /> areas;flows of 3,500 gpm for 3 hours are generally considered acceptable. <br /> (2)Based on firm capacity listed in Table 4C-754. <br /> (3)Emergency storage equals 20%of maximum day demand. <br /> City of Orono Community Management Plan 2020-2040 Part 4C, Page 13 <br />