I L <br />O COUNTY RD. 18 (SHORELINE DR.) <br />r FDC & Alarm 0 <br />Q. <br />O <br />U <br />Q <br />U <br />Static = 58 psi <br />Residual = 50 psi @ 1,185 gpm <br />Flow test elevation = <br />Upper Floor Level <br />N <br />Site Plan <br />NTS <br />BRASS <br />1 x 0-4 UPRIGHT <br />1 x VARIES <br />1X'/ELL <br />RISE <br />BRANCHLINE <br />"SWING" AS NEEDED TO <br />ALIGN SPRINKLER <br />DEFLECTOR WITH <br />PITCHED ROOF/CEILING <br />1 x VARIES <br />DROP <br />CHROME <br />PENDENT-� <br />DETAIL ATTIC UPRIGHT SPRINKLER "SWING" <br />NTS <br />GENERAL NOTES: <br />1. System designed per NFPA 13 - 2002 Edition <br />2. Building occupancy: <br />a.) All areas Light Hazard except <br />b.) Ordinary Group 2 Hazard - Mech., Elec. & Storage rooms <br />3. All materials used in the installation of this system shall be new <br />and of current issue. All materials shall be approved by U.L. and/or <br />F.M., and be in comformance with NFPA 13, as well as the authority <br />having jurisdiction. <br />4. Electrical wiring is not part of this contract and shall be performed <br />by others under seperate contract. <br />5. The graphical illustration of the locations of sprinkler devices on <br />this shop drawing is not intended (nor is it a requirement of this <br />contract) to be "aligned" at the center of ceiling tiles and/or any other <br />trade (i.e. lights, diffusers). <br />6. Painting, priming or preparation for painting of the system piping <br />and/or components is not part of this contract. <br />7. Hydrostatic testing and/or flushing of above ground piping shall be <br />performed in accordance with NFPA 13 and shall be witnessed by a <br />representative of the local authority having jurisdiction. <br />12 <br />4F <br />WOOD TRUSSES @ <br />2-0" O.C. <br />P.I.V. <br />O <br />Riser Detail <br />NTS <br />23 <br />GROOVED 90 ELBOW <br />TO SYSTEM <br />FLOW SWITCH �\ <br />PRESSURE / <br />GAUGE <br />4" GROOVED BUTTERFLY VA. <br />WI TAMPER SW. <br />4" <br />Ceiling J <br />,-Obstruction <br />10 .. <br />a <br />"Beam rule" for ISTANDARD <br />upright and pendent sprinklers <br />NFPA 13 - 1999 Edition' - Section 5-6.5.1.2 <br />DRAIN VALVE <br />OIz <br />4" GROOVED <br />CHECK VALVE <br />"V]C" FLANGE <br />FLANGE 90° <br />tq <br />Xw <br />INSPECTOR'S TEST CONNECTION <br />NTS <br />8. Installation, flushing an( testing of underground piping and <br />components is not part of his contract and shall be performed by <br />others. <br />9. In area subject to freezi 1g conditions, it is the Owner's <br />responsibilty to provide he st throughout wet pipe sprinkler system <br />areas and enclosures. <br />10. THREADED pipe 2" aid smaller to be Allied XL threadable <br />thinwall. <br />11. GROOVED pipe to be (Dyna -Flow <br />12. Hangers to be installe I in conformance with NFPA 13. This <br />contract does not include 1ny material or device to improve the <br />structural strength of the t uilding to enable it to carry the load of the <br />fire protection system. <br />13. Floor area: 3,970 sq.fl <br />14. Flow test: Static 58 ps <br />Residual 5( psi @ 1,185 gpm. <br />Flow test elev. = Uppe - floor elev. <br />15. All sprinklers to be Qu ck Response. <br />4'-4" 2 3-6" <br />2�/=" TOP OF TRUSS <br />12 4 129'-71 /4" <br />2 <br />12 <br />NEW 2" CONCRETE TOPPING <br />• NEW 8" P.C. PLANK <br />F.F.E.=109'-7 3/8" <br />BOT. 10" BEAM = <br />107'-11 3/8" <br />o, <br />NEW CONC. FLOOR SLAB <br />• F.F.E.=100'-0" <br />Section "A" <br />Scale: 1/8" = V-0" <br />allowable <br />Distance from <br />distance of deflector <br />distance <br />Sprinkler to side of <br />above bottom of <br />Obstruction (a) <br />Obstruction (b) <br />Less than 1'40" <br />0" <br />1'-0" to less than 1'-6" <br />255" <br />V-6' to less than 2'-0" <br />3'W" <br />2'-0" to lessthan 2'-T <br />555" <br />2'-6" to less than 3'-0" <br />754" <br />3-0" to less than 3'-6" <br />9W <br />3'-6" to less than 4'-(" <br />F.F.E.=109'-13/4" <br />4'-0" to less than 4'-6" <br />1'-2" <br />4-0" to less than 5'-(r <br />1455" <br />5-0" and greater <br />1' 6" <br />"Beam rule" for ISTANDARD <br />upright and pendent sprinklers <br />NFPA 13 - 1999 Edition' - Section 5-6.5.1.2 <br />DRAIN VALVE <br />OIz <br />4" GROOVED <br />CHECK VALVE <br />"V]C" FLANGE <br />FLANGE 90° <br />tq <br />Xw <br />INSPECTOR'S TEST CONNECTION <br />NTS <br />8. Installation, flushing an( testing of underground piping and <br />components is not part of his contract and shall be performed by <br />others. <br />9. In area subject to freezi 1g conditions, it is the Owner's <br />responsibilty to provide he st throughout wet pipe sprinkler system <br />areas and enclosures. <br />10. THREADED pipe 2" aid smaller to be Allied XL threadable <br />thinwall. <br />11. GROOVED pipe to be (Dyna -Flow <br />12. Hangers to be installe I in conformance with NFPA 13. This <br />contract does not include 1ny material or device to improve the <br />structural strength of the t uilding to enable it to carry the load of the <br />fire protection system. <br />13. Floor area: 3,970 sq.fl <br />14. Flow test: Static 58 ps <br />Residual 5( psi @ 1,185 gpm. <br />Flow test elev. = Uppe - floor elev. <br />15. All sprinklers to be Qu ck Response. <br />4'-4" 2 3-6" <br />2�/=" TOP OF TRUSS <br />12 4 129'-71 /4" <br />2 <br />12 <br />NEW 2" CONCRETE TOPPING <br />• NEW 8" P.C. PLANK <br />F.F.E.=109'-7 3/8" <br />BOT. 10" BEAM = <br />107'-11 3/8" <br />o, <br />NEW CONC. FLOOR SLAB <br />• F.F.E.=100'-0" <br />Section "A" <br />Scale: 1/8" = V-0" <br />BOT. OF JSTS. & <br />MAS. BRG. ELEV.= 108'-1" <br />EXISTING 12" <br />MASONRY WALL <br />EXISTING CONC. FLOOR SLAB <br />F.F.E.=100'-7" <br />TOP OF TRUSS <br />12 <br />4� <br />WOOD TRUSSES @ <br />T-0" O.C. <br />0 <br />0 <br />2' CONCRETE TOPPING <br />8" P.C. IaLANK <br />F.F.E.=109'-7 3/8' <br />97 <br />P.C. BRG. & T.O.S.=108'-9 3/8" BOT. 10" BEAM - <br />107'-11 3/8' <br />ti <br />C6 <br />NEW CONC. FLOOR SLAB <br />F.F.E.=100'-0' <br />Section "B" <br />Scale: 1/8" :=1'-0" <br />LO <br />0 <br />co <br />00 <br />Up to <br />Upper Level <br />STORAGE <br />8-9h" <br />ORD. GP. 2 <br />Insp. <br />Test <br />1" plug <br />Lower Level Sprinkler Plan <br />Scale: 1/8" = 1'-0" <br />1 5 10 <br />I 1 <br />a <br />APPROVED <br />SIDE OF "SAMMY SUPER SCREW <br />TRUSS TYPE PRODUCT <br />BALL THREAD ROD <br />�,�-PIPE RING <br />"SAMMY SUPER SCREW" <br />TYPE HANGER <br />4'-4" 2 3-E" <br />BOT. OF TRUSS <br />REVISIONS <br />ELEV.=122'-3 3/4" <br />1.617 <br />@ HIGH POINT <br />12 <br />�4 <br />X <br />SPRINKLERS THIS SHEET <br />N <br />M <br />r <br />ELEV.=120'-6" <br />SPRINKLER TYPE <br />EXISTING 3/4" FLOOR <br />EXISTING 2" CONC. TOPPING <br />EXISTING 3/4" SUBFLOOR <br />200° <br />EXISTING 2x12 @ 16" O.C. <br />U <br />F.F.E.=109'-13/4" <br />BOT. OF JSTS. & <br />MAS. BRG. ELEV.= 108'-1" <br />EXISTING 12" <br />MASONRY WALL <br />EXISTING CONC. FLOOR SLAB <br />F.F.E.=100'-7" <br />TOP OF TRUSS <br />12 <br />4� <br />WOOD TRUSSES @ <br />T-0" O.C. <br />0 <br />0 <br />2' CONCRETE TOPPING <br />8" P.C. IaLANK <br />F.F.E.=109'-7 3/8' <br />97 <br />P.C. BRG. & T.O.S.=108'-9 3/8" BOT. 10" BEAM - <br />107'-11 3/8' <br />ti <br />C6 <br />NEW CONC. FLOOR SLAB <br />F.F.E.=100'-0' <br />Section "B" <br />Scale: 1/8" :=1'-0" <br />LO <br />0 <br />co <br />00 <br />Up to <br />Upper Level <br />STORAGE <br />8-9h" <br />ORD. GP. 2 <br />Insp. <br />Test <br />1" plug <br />Lower Level Sprinkler Plan <br />Scale: 1/8" = 1'-0" <br />1 5 10 <br />I 1 <br />a <br />APPROVED <br />SIDE OF "SAMMY SUPER SCREW <br />TRUSS TYPE PRODUCT <br />BALL THREAD ROD <br />�,�-PIPE RING <br />"SAMMY SUPER SCREW" <br />TYPE HANGER <br />4'-4" 2 3-E" <br />REVISIONS <br />/tel <br />12 <br />A-1 Minnetonka Rental <br />3607 Shoreline Drive <br />Orono, MN <br />�4 <br />SPRINKLERS THIS SHEET <br />BOT. OF TRUSS <br />ELEV.=120'-6" <br />SPRINKLER TYPE <br />S.I.N. <br />EXISTING 2" CONC. TOPPING <br />1550 <br />200° <br />EXISTING 4" INSULATION <br />DAK 1 OF 1 137 City <br />Reliable F1 FR - %' Chrome Rec. Pend. <br />EXISTING 12" P.C. CONC. PLANK <br />5.6 <br />48 <br />F.F.E.=112'-4'/2" <br />48 <br />DRAWN BY SCALE DATE CONTRACT NO. <br />Reliable F1 FR -'W Brass Upright <br />R3625 <br />P.C. BRG. = 110'-10 1/2" <br />50 <br />50 <br />EXISTING <br />12" <br />R3622 <br />MASONRY WALL <br />20 <br />12 <br />EXISTING CONC. FLOOR SLAB <br />Midwest <br />FIRE PROTECTION INC. <br />324 Harding St. NE • Minneapolis, MN 55413 ■ 612-331-1411 <br />MN LICENSE #C-021 <br />Reliable F1 FR - Y4" Brass Pendent R3612 8.0 2 2 <br />Reliable F1 FR-'/" Brass Horz. Sidewall R3635 5.6 1 1 2 <br />F.F.E. VARIES <br />100'-7" TO 100'-1" <br />CALC. AREA #5 of 5 (STORAGE) <br />ORD. GP. 2 - DENSITY: 0.20 <br />AREA OF OPERATION - 900 SQ.FT. (Clg.Hgt. 8'-9%') <br />(1,500 sq.ft. reduced per NFPA 13, 2002 Edition, Sec. 11.2.3.2.3) <br />NUMBER OF SPRINKLERS CALC'ED: 9 <br />SYSTEM DEMAND: 35.51 psi, 263.77 gpm <br />HOSE ALLOWANCE: 250 gpm <br />TRUSS <br />CHORD / <br />APPROVED <br />" J ALL THREAD ROD <br />SAMMY SUPER SCREW f <br />TYPE PRODUCT <br />,,,--PIPE RING <br />"SAMMY SUPER SCREW" <br />TYPE HANGER <br />r - ► r <br />CONCRETE <br />ANCHOR <br />ALL THREAD <br />ROD <br />PIPE RING <br />CONC. ANCHOR <br />HANGER <br />D) <br />2 1/2" <br />WOOD TRUSSES <br />@ 2'-0" O.C. WOOD TRUSSES <br />@ 2'-0" O.C. <br />BOT. OF TRUSS <br />ELEV.=120'-6" <br />EXISTING 2" CONC. TOPPING <br />-b EXISTING 4" INSULATION <br />EXISTING 12" P.C. CONC. <br />F.F.E.=112'-4Y:° <br />EXISTING 3/4" FLOOR <br />N EXISTING 3/4" SUBFLOOR <br />PLANK BRG. 110'-10'/2" F.F.E.=109'-1'/: <br />EXISTING 122 <br />MASONRYV <br />EXISTING CONC. FLOOR SLAB <br />F.F.E. VARIES 100'-7" T0100'-1" <br />Section "C" <br />Scale: 1/8" =1'-0" <br />BOT. OF 2 x 12 JSTS. & <br />MAS. BRG. ELEV.=108'-1" <br />EXISTING CONC. FLOOR SLAB <br />F.F.E.= WOW" <br />CALC. AREA #4 of 5 (STORAGE) <br />ORD. GP. 2 - DENSITY: 0.20 <br />AREA OF OPERATION - 900 SQ.FT. (CIg.Hgt. T-6") <br />(1,500 sq.ft. reduced per NFPA 13, 2002 Edition, Sec. 11.2.3.2.3) <br />NUMBER OF SPRINKLERS CALC'ED: 9 <br />SYSTEM DEMAND: 35.68 psi, 282.11 gpm <br />HOSE ALLOWANCE: 250 gpm <br />STORAGE <br />7-6" Bot. of 2 x 12 M <br />ORD. GP. 2 <br />STORAGE <br />Varies 19-31/2"- 10'-9'h' <br />ORD. GP. 2 <br />4" GROOVED <br />CHECK VALVE ' <br />4" GROOVED <br />DRAIN ELL. <br />INSTALL BALL DRIP PER NFPA <br />SIAMESE <br />F.D.C. <br />Fire Dept. Connection Detail <br />NTS <br />4 <br />21-8 <br />PARTY STS <br />CALC. AREA #2 of 5 (STORAGE) <br />ORD. GP. 2- DENSITY: 0.20 <br />AREA OF OPERATION - 974 SQ.FT. (Clg.Hgt. 13'-3") j <br />(1,500 sq.ft. reduced per NFPA 13, 2002 Edition, Sec. 11.2.3.2.3) <br />NUMBER OF SPRINKLERS CALC'ED: 11 <br />SYSTEM DEMAND: 50.21 psi, 267.62 gpm <br />HOSE ALLOWANCE: 250 gpm <br />CALC. AREA #3 of 5 (STORAGE) <br />ORD. GP. 2 - DENSITY: 0.20 <br />AREA OF OPERATION - 919 SQ.FT. (Clg.Hgt. 10'-10") <br />(1,500 sq.ft. reduced per NFPA 13, 2002 Edition, Sec. 11.2.3.2.3) <br />NUMBER OF SPRINKLERS CALC'ED: 10 <br />SYSTEM DEMAND: 41.47 psi, 292.88 gpm <br />HOSE ALLOWANCE: 250 gpm <br />1 <br />33-0 <br />------ <br />- - - - - - - -- <br />REVISIONS <br />/tel <br />A-1 Minnetonka Rental <br />3607 Shoreline Drive <br />Orono, MN <br />Upper Level Sprinkler Plan <br />Scale: 1/8" = V-0" <br />1 5 10 <br />i 1 i <br />0 <br />0 <br />Daniel A. Kaiser ���u� Cly civ. • <br />SENIOR ENGINEERING TECHNICIAN I LEVEL IV <br />FIRE PROTECTION ENGINEERING TECHNOLOGY <br />AUTOMATIC SPRINKLER SYSTEM LAYOUT <br />CERTIFICATION #074000 <br />Note: Attic sprinklers to be 200° <br />Note: Interior walls extent to the bottom of <br />roof trussed unless noted otherwise. <br />N <br />MN <br />OFFICE/ <br />OUNTER <br />UNISEX <br />TOILET <br />LUNCHROOM <br />rn <br />04 <br />OFFICE <br />CALC, AREA #1 of 5 (ATTIC) <br />LlOHT HAZARD - DENSITY: 0.10 <br />AREA OF OPERATION - 1,950 80. FT., <br />NUMBER OF SPRINKLERS CALC'ED: 227 <br />SYSTEM DEMAND: 48.83 psi, 524.37 gpm <br />HOSE ALLOWANCE: 100 gpm <br />1411 A <br />CITY OF ORONO <br />BUILDING P ",,4I T r^LANE'Ji=:W y/ <br />INS FO TOR R -<C.0 T r ANC /NCr �}- � , (/ O <br />i T:D <br />T >, d r!3 <br />THIS i'L. N SE F ON eI T E AT ALL TIMES <br />DATE <br />REVISIONS <br />A-1 Minnetonka Rental <br />3607 Shoreline Drive <br />Orono, MN <br />SPRINKLERS THIS SHEET <br />SURVEYED BY SHEET NO. TOTAL HEADS JOB APPROVAL <br />SPRINKLER TYPE <br />S.I.N. <br />K -factor <br />1550 <br />200° <br />286-1 TOTAL <br />DAK 1 OF 1 137 City <br />Reliable F1 FR - %' Chrome Rec. Pend. <br />R3615 <br />5.6 <br />48 <br />48 <br />DRAWN BY SCALE DATE CONTRACT NO. <br />Reliable F1 FR -'W Brass Upright <br />R3625 <br />5.6 <br />50 <br />50 <br />DAK AS INDICATED 12/12/04 1 o -/ 7- 5 <br />Reliable F1 FR - W Brass Upright <br />R3622 <br />8.0 <br />20 <br />12 <br />3 1 35 <br />Midwest <br />FIRE PROTECTION INC. <br />324 Harding St. NE • Minneapolis, MN 55413 ■ 612-331-1411 <br />MN LICENSE #C-021 <br />Reliable F1 FR - Y4" Brass Pendent R3612 8.0 2 2 <br />Reliable F1 FR-'/" Brass Horz. Sidewall R3635 5.6 1 1 2 <br />