Laserfiche WebLink
� <br /> 5��_�-�r IntelliKni ht 5700 Batte Calculation <br /> KN����-�- 9 rY <br /> Note 1: You are full res onsible for verif in these calculations. <br /> �'''H6l�� Note 2: Use the dropdowns in the yellow cells to enter values. <br /> Calculation in Total Sheet <br /> -. -. . . . <br /> 24 Hours <br /> Standb Load Current 0.20135 Amps x 24 = 4.832 AH <br /> -. -. <br /> 5 Minutes <br /> Alarm Load Current Amps) 0.91235 Am s x 0.084 = 0.077 AH <br /> Total Current Load 4.909 AH <br /> Multi I b the Deratin Factor 1.2 = x 1.20 <br /> Total Ampere Hours Required 5.89 AH <br /> Recommended Batteries: BAT-1270 -7AH Batteries <br /> The batteries can be char ed b the 5700 Char er. <br /> The batteries can be housed in the 5700 Cabinet. <br /> . � _ _ <br /> Circuit#1 current is within the limitations of the circuit. <br /> Circuit#2 current is within the limitations of the circuit. <br /> 5700 Control Panel: <br /> The output current is within the anel's limitations. <br /> Silent Knight by Honeywell Page 3 7/15/2016 <br />