Laserfiche WebLink
� Job:The Woofington Hydraulic Calculations <br /> PIPE INFORMATION <br /> Node 1 Elev 1 K-Factor 1 Flow added (q) Nominal ID Fittings L C Factor total (Pt) f <br /> Node 2 Elev 2 K-Factor 2 Total flow (Q) Actual ID quantity x (name) = length F Pf per ft elev (Pe) NOTES <br /> T frict(P� � <br /> (ft) (gpm/psi�/z) (gpm) (in) (ft) (ft) (psi) (psi) �.� <br /> Path No: 13 <br /> S27 8.75 5.6 23.1 1 2x(VIC.90)=5.13 1.13 120 17 <br /> 170 9.33 23.1 1.104 5.13 0.1319 -0.3 <br /> 6.26 0.8 <br /> 170 9.33 0 1 lx(VIC.TEE-Br)=5 0.17 120 17.6 <br /> 163 9.17 23.1 1.049 5 0.1691 0.1 <br /> 5.17 0.9 <br /> 163 18.5 <br /> Path No: 14 <br /> 079 9.75 0 2 lx(VIC.90)=6.82 7.14 120 23.4 <br /> 066 9.75 2.6 2.203 6.82 0.0001 0 <br /> 13.96 0 <br /> 066 23.4 <br /> * Pressures are balanced to a high degree of accuracy. Values may vary by 0.1 psi due to display rounding. <br /> * Maximum Velocity of 17.13 ft/s occurs in the following pipe(s): (066-173) <br /> File:O:\Projects\2130-370491 The Woofington\Design\CFSP\The Woofington-submit.dwg <br /> Date 4/22/2016 Copyright�2002-2012 Tyco Fire Protection Products PBge 23 <br />