Laserfiche WebLink
Job:The Woofington ' <br /> Hydraulic Analysis for : 1 <br /> Graph Labels <br /> La bel Descri ption Va I ues <br /> Flow (gpm) Pressure (psi) <br /> S1 Supply point#1 -Static 0 63 <br /> S2 Supply point#2-Residual 1089 59 <br /> D1 Elevation Pressure 0 3.9 <br /> D2 System Demand 275.4 53.4 <br /> D3 System Demand+Add.Out.Hose 525.4 53.4 <br /> Curve Intersections 8� Safety Margins <br /> Intersection Safety Margin <br /> Curve Name <br /> Pressure (psi) Flow (gpm) Pressure (psi) @ Flow (gpm) <br /> Supply 62.6 302 8.6 525.4 <br /> Open Heads <br /> Required Calculated <br /> Head Ref. Head Type Coverage K-Factor <br /> Density Flow Pressure Density Flow Pressure <br /> (sq.ft) (gpm/psi�h) (gpm/sq.R) (gpm) (psi) (gpm/sq.ft) (gpm) (psi) <br /> Si Overhead 120 5.6 0.2 24 18.4 0.204 24.5 19.1 <br /> Sprinkler , <br /> S10 Overhead 124.4 5.6 0.2 24.9 19.7 0.204 25.4 20.6 <br /> Sprinkler • <br /> S11 Overhead 137.6 5.6 0.1 13.8 7 0.181 24.9 19.8 <br /> Sprinkler <br /> SZ Overhead 120 5.6 0.2 24 18.4 0.211 25.3 20.4 <br /> Sprinkler <br /> S3 Overhead 120 5.6 0.2 24 18.4 0.217 26.1 21.7 <br /> Sprinkler <br /> S4 Overhead 120 5.6 0.2 24 18.4 0.218 26.1 21.7 <br /> Sprinkler <br /> SS Overhead �$� 5.6 0.2 15.7 7.9 0.321 25.3 20.3 <br /> Sprinkler <br /> S6 Overhead 78� 5.6 0.2 15.7 7.9 0.298 23.5 17.6 <br /> Sprinkler <br /> S� Overhead 120 5.6 0.2 24 18.4 0.2 24 18.4 <br /> Sprinkler � <br /> S8 Overhead 120 5.6 0.2 24 18.4 0.207 24.8 19.6 <br /> Sprinkler <br /> S9 Overhead 124.4 5.6 0.2 24.9 19.7 0.206 25.6 20.9 <br /> Sprinkler <br /> File:O:\Projects�2130-370491 The Woofington\Design\CFSP\The Woofington-submit.dwg <br /> Date 4/22/2016 Copyright�2002-2012 Tyco Fire Protection Products Page 6 <br />