Laserfiche WebLink
Standby Battery Calculations <br /> MS-9050UD <br /> Advance Auto Parts <br /> Navarre, MN 55392 <br /> Standby Current Alarm Current <br /> Part Number Descri tion Quanti Per Device All Devices Per Device All Devices <br /> MS-9050UD Addressable Fire Alarm Control Panel 1 0.120000 0.120000 0.020000 0.020000 <br /> SD355 Smoke Detector Photo 1 0.120000 0.120000 0.020000 0.020000 <br /> BG-12LX Manual Pull Station Addressable 1 0.000300 0.000300 0.000300 0.000300 <br /> MMF-300 Monitor Module Single input 3 0.000400 0.001200 0.005100 0.015300 <br /> ._._.�__._..................... ........................................... <br /> Total Aux current Max 3 Amps 0.242 Alarm 0.056 <br /> Si nal Circuits <br /> Current Current <br /> Circuit Device Quanti Per Device All Devices <br /> Circuit 1 <br /> P2R-110 1 0.212 0.212 <br /> ....................................................._,,...,,,,......,,.,,....,... <br /> Total 1 Maximum 2.5 Amps 0.212 <br /> Circuit 2 Not Used <br /> .................................................................�...,..._....._ <br /> Total 2 Maximum 2.5 Amps 0.000 <br /> Totals Maximum 2.7 Am s 0.212 <br /> Circuit 1 Circuit 2 <br /> Max Wire Run Distance For AWG 14 3073 <br /> Actual Wire run Distance 50 0 <br /> Voltage Drop for 14 AWG wire 0.065 <br /> Volta e Dro =2'Wire Run Distance`3.07 Ohms Per 1000 ft 14 AWG'Total Current for Circuit/1000 <br /> Standby Hours 24 <br /> Standby Battery Draw 0.242 <br /> Standb Amp Hrs 5.796 <br /> Alarm Current 0.212 <br /> Alarm Current 5 Min 0.018 <br /> Battery Size Required <br /> with 5 Min.Alarm Time <br /> and 20%Reserve 6.976 <br /> Batte Size Supplied 10 A.H <br />