Laserfiche WebLink
, Fir�a�.Calculations - Hazen-Williams <br /> Page 6 <br /> � LOUN�R LEVEL Date <br /> Hyd. c`�a via. Fitting Pipe Pt Pt <br /> , _ _ ._, .._ , �„ <br /> Ref. "C" or Ftng's Pe Pv """*** Notes *'*"'`'` <br /> Point Qt Pf/Ft Eqv. Ln. Total Pf Pn <br /> 31 64.85 2.067 0.0 9.000 19.220 <br /> to 120.0 0.0 0.0 0.0 <br /> 35 153.01 0.2063 0.0 9.000 1.857 Vel = 14.63 <br /> 35 67.83 2.067 21 7.0 6.000 21.077 <br /> to 120.0 0.0 7.000 0.0 <br /> 36 220.84 0.4069 0.0 13.000 5.290 Vel = 21.11 <br /> 36 0.0 2.635 I 8.237 18.000 26.367 <br /> to 120.0 0.0 8.237 0.0 <br /> 37 220.84 0.1247 0.0 26.237 3.273 Vel = 12.99 <br /> 37 0.0 3.26 11 E 103.484 60.000 29.640 <br /> to 120.0 0.0 103.484 5.197 <br /> BAS 220.84 0.0442 0.0 163.484 7.233 Vel = 8.49 <br /> BAS 0.0 4.026 2B 24.0 2.000 42.070 , <br /> to 120.0 S 22.0 46.000 0.0 <br /> SPG 220.84 0.0158 0.0 48.000 0.759 Vel = 5.57 <br /> SPG 0.0 4.1 E 14.534 300.000 42.829 <br /> to 140.0 G 2.907 46.508 0.0 <br /> HYD 220.84 0.0109 T 29.067 346.508 3.774 Vel = 5.37 <br /> HYD 100.00 4.1 0.0 1.000 46.603 Qa= 100 <br /> to 140.0 0.0 0.0 0.0 <br /> CITY 320.84 0.0220 0.0 1.000 0.022 Vel = 7.80 <br /> 0.0 <br /> 320.84 46.625 K Factor= 46.99 <br /> Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 <br />