Laserfiche WebLink
Finai Calculations - Hazen-Williams <br /> Page 6 <br /> LOWER LEVEL GARAGE Date <br /> Hyd. Qa Dia. Fitting Pipe Pt Pt <br /> Ref. "C" or Ftng's Pe Pv ""*'**' Notes ""***" <br /> Point Qt Pf/Ft Eqv. Ln. Total Pf Pn <br /> BAS 0.0 4.31 2B 33.449 2.000 43.264 <br /> to 120.0 S 30.661 64.110 0.866 <br /> SPG 245.4 0.0138 0.0 66.110 0.912 Vel= 5.40 <br /> SPG 0.0 6.16 21 28.692 100.000 45.042 <br /> to 140.0 G 4.304 32.996 0.0 <br /> HYD 245.4 0.0018 0.0 132.996 0.243 Vel= 2.64 <br /> HYD 250.00 6.16 T 43.037 300.000 45.285 Qa=250 <br /> to 140.0 0.0 43.037 0.0 <br /> CITY 495.4 0.0067 0.0 343.037 2.293 Vel= 5.33 <br /> 0.0 <br /> 495.40 47.578 K Factor= 71.82 <br /> Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 <br />