j�� <br /> , BUILDING LEAKAGE TEST Page 3 of 4 <br /> Date of Test: 3/12/2018 Test File: 1750 Shadywood Road <br /> Depressurization Test: <br /> Environmental Data <br /> Indoor Temperature(°F) Outdoor Temperature(°F) <br /> 70.0 31.0 <br /> Data Points -Automated Test(TT 4.0.48.0) <br /> Nominal Baseline Adjusted Fan Nominal Adjusted <br /> Building Pressure Building Pressure Pressure Flow Flow Fan <br /> (Pa) (Pa) (Pa) (cfm) (cfm) °/a Error Configuration <br /> -2.4 n/a n/a <br /> -27.0 -24.7 217.1 872 840 -2.6 Ring B <br /> -32.3 -30.0 295.6 1017 979 -1.4 Ring B <br /> -37.1 -34.8 359.7 1121 1079 -2.2 Ring B <br /> -42.7 -40.4 53.3 1321 1271 3.4 Ring A <br /> -48.0 -45.7 61.9 1421 1368 1.8 Ring A <br /> -56.2 -53.9 78.0 1591 1531 1.0 Ring A <br /> -64.6 -62.3 94.0 1742 1677 -0.3 Ring A <br /> -72.7 -70.4 110.4 1884 1813 -1.3 Ring A <br /> -2.2 n/a n/a <br /> Deviations from Standard CGSB -Test Parameters <br /> - One or more of the test data points was taken at a building pressure that differed by more than 2.5 <br /> Pascals from the target pressure. <br /> i <br /> ( <br /> I <br /> I <br />