Laserfiche WebLink
, �- <br /> Special Provisions for Assembly Areas: (UBC 303.2.2.2) <br /> Division 3 Occupancies located in a basement or above the first floor shall not be <br /> of less than 1-hour fire resistive construction. (Complies) <br /> Division 3 Ocupancies with an occupant load of 50 or more which are located <br /> over usable space shall be separated from such space by not less than 1-hour fire <br /> resistive construction. (Complies) <br /> Exiting: <br /> Minimum Width <br /> Assembly Room: <br /> Horizontal travel: 274 persons * 0.2 inches/person = 55"required <br /> Two exits provided. Each at 36" width =72" total width provided <br /> Complies. <br /> Stairs: Assuming exterior exit stair from Sanctuary will serve half <br /> of the occupant load <br /> 137 persons * 0.3"/person =41.1"required width <br /> 44" actual stair width provided. <br /> Complies <br /> Horizontal Exit: <br /> The Assembly Space has one exit directly to the exterior and one exit <br /> through the Lobby space. A two hour occupancy separation wall with a <br /> 90 minute fire rated door assembly will be installed near the central stair <br /> where indicated on the plans to form a horizontal exit between the <br /> assembly portions of the building and the remaining building. The door <br /> will have magnetic hold opens with closing actuation by actuation of a <br /> smoke detector on either side of the door. Please refer to UBC 1005.3.5.1 <br /> Refuge Area: Assuming exiting for half of the assembly occupant load <br /> 137 persons * 3 Sq. Ft/person =411 Square Feet refuge required <br /> Refuge Provided= 144 Sq.Ft. Hallway <br /> 196 Sq. Ft. Upper Level Lobby <br /> 168 Sq. Ft. Lower Level Lobbv <br /> 508 Sq.Ft.Actual Area of Refug�e Space <br /> Complies <br />