Laserfiche WebLink
SYSTEM RECORD OF COMPLETION (continued) <br /> 5. SYSTEM POWER <br /> 5.1 Control Unit <br /> 5.1.1 Primary Power <br /> Input voltage of control panel: 120VAC Control panel amps: 3 <br /> Overcurrent protection: Type: Breaker Amps: 20 <br /> Branch circuit disconnecting means location: Elec. Rm Number: PNL 1 CKT 8 <br /> 5.1.2 Secondary Power <br /> Type of secondary power: Battery SLA <br /> Location,if remote from the plant: <br /> Calculated capacity of secondary power to drive the system: <br /> In standby mode(hours): 24 In alazm mode(minutes): 10 <br /> 5.2 Control Unit <br /> � This system does not have power extender panels <br /> ❑ Power extender panels are listed on supplementary sheet A <br /> 6. CIRCUITS AND PATHWAYS <br /> Pathway Type Dual Media Pathway Separate Pathway Class Survivability Level <br /> Signaling Line B <br /> Device Power <br /> Initiating Device <br /> Notification Appliance B <br /> Other(specify): <br /> 7. REMOTE ANNUNCIATORS <br /> Type Location <br /> Silent Knight 5860 Front Door <br /> 8. INITIATING DEVICES <br /> Addressable or <br /> Type Quantity Conventionai Alarm or Supervisory Sensing Technology <br /> Manual Pull Stations 2 Addressable Alarm N/A <br /> Smoke Detectors 18 Addressable Alarm Yes <br /> Duct Smoke Detectors <br /> Heat Detectors <br /> Gas Detectors <br /> Waterflow Switches <br /> Tamper Switches <br /> Copyright�2012 National Fire Protection Association.This form may be copied for individual use other than for resale.It may not be copied for commercial sale or distribution. <br /> tp. 2 of 3} <br />