AC.RasideMlal�L(gM Commerclal HVAG Lwds ProQam .;� Elifo Soflwaro Dwelop�rwM,Jnc.
<br /> . ,Aa�Aire .: -: _ : ,: , , l�LLY/KL.INE
<br /> ;egen,NqV 55123 ` - ` 05-30-2001 _ PaBe 2
<br /> System#1 Summary Loads
<br /> Componerrt Area Sen. Lat. Sen. Total
<br /> Description Quan Loss Gain Gain Gain
<br /> 3D Window Double Pane Low Emit Wood Frame 1,332 44,239 0 63,380 63,380
<br /> 11E Door Metal Urethane Core 42 734 0 188 188
<br /> 12H Wali R-19+ 1/2"Gypsum Board(R-0.5) 3,575 19,734 0 5,060 5,060
<br /> 15G Wall 5'or More Below Grade 8/12"BIk+R-11 1,621 6,413 0 0 0
<br /> 16H Ceiling R-38 Insulation 3,318 7,937 0 3,796 3,796
<br /> 201 Floor Over Open Crawl Carpet+R-19 448 1,978 0 323 323
<br /> 21A Basemt Floor 2'or More Below Grade 2,870 6,337 0 0 0
<br /> Subtotals for stn�cture: 13,206 87,372 0 72,747 72,747
<br /> Active People: 4 0 920 1,200 2,120
<br /> Inactive People: 0 0 0 0 0
<br /> Appliance.s: 0 0 0 0 0
<br /> Lighting: 0 0 0 0 0
<br /> Ductwork: 0 431 0 378 378
<br /> Infiltration:Wirrter CFM:405.4, Summer CFM: 135.1 1,374 39,803 3,208 2,884 6,092
<br /> Verrtilation:Wirrter CFM: 135.1, Summer CFM: 135.1 0 13,267 3,209 2,884 6,093
<br /> Sensible Gain Total: 80,093
<br /> Temperature Swing Mumplier. X1.00
<br /> System Load Totals: 140,873 7,337 80,093 87,430
<br /> :: _._...',.,.� ���,���_,�..� v.:
<br /> �ecCt.�`igu�e� ,_.�; .. .,_ ,,� .- .,�.�.,,,.� - _
<br /> _ . ,.. _ _ �_ � ._...�.....
<br /> � :: �: .
<br /> . , ..: ,
<br /> �
<br /> � ; _.� ��� .
<br /> Supply CFM: 3,617 CFM per square foot: 0.399
<br /> Square feet of room area: 9,058 Square feet per ton: 1,044.981
<br /> - ,.��-- , : �._
<br /> �" ` f k�,.,���u� .�.� � �
<br /> �Et'��t3��°'" �..�,�:�.. .__... .__..�._.�. ��.�-'�r ._._ _.��-,. �.,;.�.�. k �:°, ,. '; . .��..�_., ;'. -
<br /> Total heating required with outside air. 140,873 Btuh 140.873 MBH
<br /> Total sensible gain: 80,093 Btuh 92 %
<br /> Total laterrt gain: 7,337 Btuh 8 %
<br /> Total cooling required with outside air. 87,430 Btuh 7.286 Tons(based on sensible+laterrt)
<br /> 8.668 Tons(based on 77%sensible capacity)
<br /> �e � �� �-� ���.. ��� �.�.�,�,�k;:�.�,.�s;�, � .,�:� : � � -
<br /> ��:: ._. _. , �:: � � ��..�.�-���._��,��.. . :'.. �,, �>
<br /> Calculations are based on 7th edition of ACCA Manual J.
<br /> All computed results are estimates as building use and weather may vary.
<br /> Be sure to select a unit that meets both sensible and laterrt loads.
<br /> Wednesday,AAaY 30.2001