<br /> Air Handler number: 1 Zone occurrences: 1 �
<br /> Zone fength: (feet) 20.74 Zone width (feet): 20.74 '
<br /> Lighting Watts: 215 Equipment Watts: 1,29�
<br /> ' Number of people in zone: 3 People profle number: 2
<br /> Lighting profile number. 0 Equipmenf profife number: 0
<br /> Ceiling height(feet): 10 Heating safety facfor(%): 15 ,
<br /> � Sensible safety factor(%): 10 Latent safety factor(%): 10 ',
<br /> I Sensible heat per person (Btuh): 250 Latent heat per person (Btuh): 200
<br /> ; Cooling ventilation method: CFM/Pr Cooling ventiiation value: 15.000 �
<br /> j Caoling infiltration method: AC/Hr Cooling infiltration value: 0.000 i
<br /> I Heating ventilation method: CFM/Pr Heating ventilation value: 15.000 ;
<br /> j Heating infiltration method: AC/Hr Heating infiltration value: 0.000 '
<br /> � Winter exhaust air CFM: 0 Summer exhaust air CFM: 0
<br /> � Minimum supply CFM: 0 Latent Btuh equipment laad: 0
<br /> '; Ceil. exposed to plenum (sq.ft): 430 Exposed floor slab perimeter(ft}: 0
<br /> ', Both heating and cooiing loads are calculated for this zone. ,
<br /> �
<br /> I, Wall �pe _ASHRAE# U-Factor Color Height Width Area Direction
<br /> 1 1 D 0.040 M 10.50 22.25 233.6 S
<br /> 2 1 D O.Q40 M 10.50 15.25 160.1 E
<br /> 3 1 D 0.040 M 10.50 7.00 73.5 E
<br /> Glass Type S.U-F. Shd C.___Height Width Quan Area Shade Tik Ref i
<br /> 1 3 0.500 0.600 4.00 7,33 1,000 29.3 0 90 2 '
<br /> I
<br /> i
<br /> .�..�__Y,.,�._.�...._.� .. a._�_ .�_...�......_.!.33L-i 1 .''�Y... .•K .R� ..fi'�S�M.......o......'',.� . ,.-�l,..:. ."''t,:'
<br /> � Air Handler number_ , 2 Zone occurrences: 1 � �
<br /> Zone length: (feet) 20.74 Zone width (feet), 20.74 �
<br /> Lighting Watts: 1 Equipment Watts: 1 �
<br /> Number of people in zone: 2 Peopfe profile number. 2
<br /> Lighting profile number: 0 Equipment profile number: 0
<br /> Ceili�g heighl (feet): 10 Heating safety factor(%): 15 ,
<br /> Sensible safety factor(%): 10 Latent safety factor(%): 10 j
<br /> , Sensible heat per person (Btuh): 250 Latent heat per person (Btuh): 200 ,
<br /> i Cooling ventilation method: CFM/Pr Cooling ventilation value: 15.000 ,
<br /> Cooling infilt�ation method; AC/Hr Cooling infiltration value: 0.000 �
<br /> Heating ventilation method: CFM/Pr Heating ventilation value: 15.000
<br /> Heating infiltration rnethod: AC/Hr Heating infiltration value: 0.000 !
<br /> Winter exhausk air CFM: 0 Summer exhaust air CFM: 0 �
<br /> Minimum supply CFM: 0 Latent Btuh equipment load: 0 '
<br /> Ceil. exposed to plenum (sq.ft): 430 Exposed floor slab perimeter (ft}: 0
<br /> Both heating and cooling loads are calculated for this zone.
<br /> Roof Type ASHRAE# U-Factor Dark Length Width Area Susp.Ceil ;
<br /> 1 1 13 0.�40 No 8.32 8.32 69.2 No !
<br /> 2 2 2 0.370 No 16.50 23.16 362.1 No ;
<br /> Wall Type ASHRAE# U-Factor Color Height Width Area Direction �
<br /> 1 2 D 0.053 M 10.50 22.25 233.6 S
<br /> � 2 2 D 0.a53 M 10.50 15.25 160.1 W
<br /> 3 2 D 0.053 M 10.50 7.00 73.5 S ,
<br /> I
<br /> � Glass Type S.U-F. Shd C, Height Width Quan Area Shade Tilt Ref
<br /> C:IELEC-CAT1EIitelChvacw321ProjectslBrenshell-Hvac.CHV Fnday,March 19,2004,8:35 AM