. Rhvac-Resldeni�al 8 Light Canmere�l HVAC 4oada Elibe Software Devalopn►ent,inc.
<br /> � Sabre Plumbing�Heating � ' 7607
<br /> P mouth N 55447 ' Pa e 4
<br /> -- ---
<br /> Tota! Building Summary Loads _ �
<br /> k i R m *g� �"� y �ey � '��
<br /> F y� 4
<br /> ����� A�y� 3 ��..� R �'- hs.z'��fi t ,1 �",� h.Y ��'� �� ;. '� fi� -�� ��,...� f � �•1� F,". "T��-� f I>d �
<br /> ,^ . .`
<br /> , ����� �,..�`�, �! s �� .� *�� , ,� , .- �� ' n �� � 1�3; d J ts i �s � pl r
<br /> �,b� �� �
<br /> , „ ,. , .. :. _ �' ,. ... �� : :, r „
<br /> LOW EE: Glazing-Builder Grade Low E Windows 8� 405.5 11,292 0 11,455 f 11,455
<br /> Sliding Door.32 U value .30 SHGC, u-value 0.32,
<br /> SHGC 0.3
<br /> 11J: Door-Metal-Fiberglass Core 37.8 1,972 0 544 544
<br /> 15A-10sffc-8: Wall-Basement, concrete block wall, R-10 1240 4,531 0 0 0
<br /> foam board to floor, no framing, no interior finish,
<br /> filled core, 8'floor depth
<br /> R-2012F-Osw: Wall-Frame, Custom, no board insulation, 2978.7 17,103 � 0 2,614 2,614
<br /> siding finish, wood studs
<br /> RJ R20 Closed Cell:Wall-Frame, Custom, Spray Foam R- 516 2,244 0 400 400
<br /> 20
<br /> R49-16B-49: Roof/Ceiling-Under Attic with Insulation on 1662 3,326 0 1,835 1,835
<br /> Attic Floor(atso use for Knee Walls and Partition
<br /> Ceilings), Custom, R49 Blown Insulation-vented
<br /> attic, asphalt shingles
<br /> 21A-20-c: Floor-Basement, Concrete slab, any thickness, 1360 3,195 0 0 0
<br /> 2 or more feet below grade, no insulation below floor,
<br /> carpet covering, shortest side of floor slab is 20'wide
<br /> 20P-19-c: Floor-Over open crawl space or garage, 1662 7,230 0 665 665
<br /> Passive, R-19 blanket insulation, carpet covering
<br /> Subtotals for structure: 50,893 0 17,513 17,513
<br /> People: 5 1,000 1,150 2,150
<br /> Equipment: 901 4,116 5,017
<br /> Lighting: 1250 4,263 4,263
<br /> Ductwork: 2,668 217 546 763
<br /> Infiltration: Winter CFM: 0, Summer CFM: 0 0 0 0 0
<br /> Ventilation:Winter CFM: 180, Summer CFM: 180 6,685 4,177 999 5,175
<br /> Humidification �nter) 16.39 gal/day : 6,010 0 0 0
<br /> AED Excursion: 0 0 708 708
<br /> Total Building Load Totals: 66,255 6,295 29,295 35,590
<br /> '�� ,:�z� r.`�r t�..,� �.t. .'�, .� ��. �,,.�1� .u.s�.,: .�� ,.'4.:. ��' G k �„��. u �i,'��,;�'�.�
<br /> 3 v.3K.. ` 9,'&�..w Y'�r� �.�3�,
<br /> Total Building Supply CFM: 1,322 CFM Per Square ft.: 0.302
<br /> Square ft. of Room Area: 4,382 Square ft. Per Ton: 1,478
<br /> Volume(ft9)of Cond. Space: 39,438
<br /> , ,
<br /> .. F
<br /> � �
<br /> y � . r 32 �" :.:: s..r*`r��:F r,.' :.k''....�F.. . .,�;; f ;,�� :.,A�'Kr� f ;��;,+,>''rr s���"� ...a,;`.,�; u`'���'�
<br /> '�rS �_
<br /> Total Heating Required Including Ventilation Air: 66,255 Btuh 66.255 MBH ^
<br /> Total Sensible Gain: 29,295 Btuh 82 %
<br /> Total Latent Gain: 6,295 Btuh 18 °�
<br /> Total Cooling Required Including Ventilation Air: 35,590 Btuh 2.97 Tons(Based On Sensible+ Latent)
<br /> H ` 'S<f ' '.�. , �
<br /> �t`sbr k.� .. ,c.. ��,,�i.,°`�v,i y,�`r„-s`�,y �. • i .a�;r -- a �` � b�_ .
<br /> - ,�.:� n�; E �*,', �� rsx-.�.tr' �, ,� �+'. ..��" t f}k*.:.LL„�+ �'„��i�� �'-''%
<br /> _ Y,z=
<br /> Rhvac is an ACCA approved Manual J and Manual D computer program.
<br /> Calculations are performed per ACCA Manual J 8th Edition,Version 2, and ACCA Manuai D.
<br /> All computed results are estimates as building use and weather may vary.
<br /> Be sure to select a unit that meets both sensible and latent loads according to the manufacturer's performance data at
<br /> your design conditions.
<br /> M:\Sales and Estimating\Heat Cafcs�David Weekley Homes\�UNTTLO.rh9 Thursday, December 08,2016, 4:26 PM