Laserfiche WebLink
` RHYAC-R�sidentl C&Light Commercial HVAC Loads Program +w Elite Sofrware Development,lnc. <br /> Ditter,Inc. GiLMORE <br /> Hamel,MN 5534Q- 691 4/1/37 Page 2 <br /> System#1 Su ' mary loads <br /> Component Area Sen. Lat. Sen. Total <br /> Description Quan Loss Gain Gain Gain <br /> 3A WindovV� Double Pane Clear Glass Wood Frame 158 8,010 0 6,302 6,302 <br /> 8M Glass qoor pouble Clear Glass Wood Frame 189 9,581 0 8,694 8,694 <br /> 11 E Door Metal Urethane Core 42 734 0 188 188 <br /> 12D Wall R-11 + 1/2"Asphlt Board(R-1.3) 1,584 11,658 0 2,992 2,992 <br /> 12H Wall Ry19 + 1/2" Gypsum Board(R-0.5) 2,603 14,369 0 3,686 3,686 <br /> 161 Ceiling R-44 lnsulation 1,680 3,555 0 1,700 1,700 <br /> 21A Basem� Floor 2' or More Below Grade 1,680 3,709 0 0 0 <br /> Subtotals for$tructure: 7,936 51,616 0 23,562 23,562 <br /> Active People�: 6 0 1,380 1,800 3,180 <br /> Inactive People: 0 0 0 0 0 <br /> Appliances: 0 0 0 1,200 1,200 <br /> Lighting: 0 0 0 <br /> Ducfinrork: 0 0 0 0 0 <br /> Infiltration: lMinter CFM: 218.4, Summer CFM: 145.6 389 22,102 3,563 3,203 6,766 <br /> Ventilation: �nter CFM: 50.0, Summer CFM: 50.0 0 5,060 1,224 1,100 2,324 <br /> Sensible Gain Total: 30,865 <br /> Temperature Swing Multiplier: X1.00 <br /> System Loac� Totals: 78,778 6,167 30,865 37,032 <br /> Check Figu es <br /> Supply CFM: 1,403 CFM per square foot: 0.418 <br /> Square feet of room area: 3,360 Square feet per ton: 1,005.877 <br /> System Lo ds ° <br /> Total heating required with outside air: 78,778 Btuh 78.778 MBH <br /> Total sensible gain: 30,865 Btuh 83 % <br /> Total latent gain: 6,167 Btuh 17 % <br /> Total coolin,g required with outside air: 37,032 Btuh 3.086 Tons (based on sensible + latent) <br /> 3.340 Tons (based on 77% sensible capacity) <br /> Notes f <br /> Calculations are based on 7th edition of ACCA Manual J. <br /> All comput�d results are estimates as building use and weather may vary. <br /> Be sure to�select a unit that meets both sensible and latent loads. <br />