<br /> Rhvac-Residential 8�Light Commercial HVAC Loads Elite Software Development,Inc.
<br /> Sabre Plumbing&Heatinq � 600 Pinehurst Court Orono
<br /> Plymouth MN 55447 _____ _ __ Pa e 4
<br /> Total Building Summary Loads
<br /> Component Area Sen Lat Sen Total
<br /> Descri tion Quan Loss Gain Gain Gain
<br /> Low EE: Glazing-LowEE Builder Grade .31 U-value, .29 811.5 21,888 0 21,859 21,859
<br /> SHGC, Window and Patio Door, u-value 0.31, SHGC
<br /> 0.29
<br /> LOW EE: Glazing-Builder Grade Low E Windows& 114.2 3,181 0 2,945 2,945
<br /> Sliding Door .32 U value .30 SHGC, u-value 0.32,
<br /> SHGC 0.3
<br /> 11J: Door-Metal - Fiberglass Core 69.3 3,620 0 999 999
<br /> 15A-10sffc-8: Wall-Basement, concrete block wall, R-10 1026 4,072 0 91 91
<br /> foam board to floor, no framing, no interior finish,
<br /> filled core, 8'floor depth
<br /> 15A-10sffc-4: Wall-Basement, concrete block wall, R-10 172 748 0 0 0
<br /> foam board to floor, no framing, no interior finish,
<br /> filled core, 4'floor depth
<br /> R20 12F-Osw: Wall-Frame, Custom, R-20 Insulation in 3324.7 19,088 0 2,917 2,917
<br /> 2x6 Cavity, no board insulation, siding finish, wood
<br /> studs
<br /> RJ 20 Spray Foam: Wall-Frame, Custom, Rim Joist R-20 583.5 2,540 0 716 716
<br /> Closed Cell Spray Foam
<br /> R-20 12F-Osw: Wall-Frame, Custom, no board insulation, 1253.2 7,196 0 1,100 1,100
<br /> siding finish, wood studs
<br /> R49 16B-49: Roof/Ceiling-Under Attic with Insulation on 2543 5,089 0 2,807 2,807
<br /> Attic Floor(also use for Knee Walls and Partition
<br /> Ceilings), Custom, R-49 Blown Insulation, No
<br /> Radiant Barrier, Vented Attic, Asphalt Shingles
<br /> R49- 16B-49: Roof/Ceiling-Under Attic with Insulation on 624 1,249 0 689 689
<br /> Attic Floor(also use for Knee Walls and Partition
<br /> Ceilings), Custom, R49 Blown Insulation-vented
<br /> attic, asphalt shingles
<br /> 21A-20: Floor-Basement, Concrete slab, any thickness, 2 1624 3,815 0 0 0
<br /> or more feet below grade, no insulation below floor,
<br /> any floor cover, shortest side of floor slab is 20'wide
<br /> 20P-30: Floor-Over open crawl space or garage, Passive, 651 1,982 0 182 182
<br /> R-30 blanket insulation, any cover
<br /> 21A-20-c: Floor-Basement, Concrete slab, any thickness, 624 1,466 0 0 0
<br /> 2 or more feet below grade, no insulation below floor,
<br /> carpet covering, shortest side of floor slab is 20'wide
<br /> Subtotals for structure: 75,934 0 34,305 34,305
<br /> People: 6 1,200 1,380 2,580
<br /> Equipment: 901 4,116 5,017
<br /> Lighting: 1250 4,263 4,263
<br /> Ductwork: 5,246 474 1,189 1,663
<br /> Infiltration: Winter CFM: 129, Summer CFM: 0 12,001 0 0 0
<br /> Ventilation: Winter CFM: 213, Summer CFM: 213 7,911 4,942 1,182 6,124
<br /> Humidification (Winter) 24.44 gal/day : 8,961 0 0 0
<br /> AED Excursion: 0 0 4,903 4,903
<br /> Total Building Load Totals: 110,053 7,517 51,337 58,854
<br /> Check Fi ures
<br /> Total Building Supply CFM: 2,342 CFM Per Square ft.: 0.365
<br /> Square ft. of Room Area: 6,415 Square ft. Per Ton: 1,308
<br /> Volume (ft') of Cond. Space: 63,680
<br /> Bu_ilding Loads
<br /> Total Heating Required Including Ventilation Air: 110,053 Btuh 110.053 MBH
<br /> Total Sensible Gain: 51,337 Btuh 87 %
<br /> Total Latent Gain: 7,517 Btuh 13 %
<br /> Total Cooling Required Including Ventilation Air: 58,854 Btuh 4.90 Tons (Based On Sensible + Latent)